“StartP
-
StopP” –
Start Pulse
–
Stop Pulse
3-wire connection (pulse control):
DIN1: closed contact = start pulse
DIN2: open contact = stop pulse, falling edge.
Start 1
Start 2
Freq. Out
Figure 7-8. Start pulse/ Stop pulse.
The selections including the text
'Rising edge required to start'
must be used to
exclude the possibility of an unintentional start when, for example, power is connected,
re-connected after a power failure, after a fault reset, after the drive is stopped by Run
Enable (Run Enable = False) or when the control place is changed. The Start/Stop
contact must be opened before the motor can be started.
4
“Strt
-
MotP UP” –
Start
–
Motor potentiometer UP
DIN1: closed contact = start forward
DIN2: closed contact = Increases motor potentiometer reference, see Motor
potentiometer function for more details.
5
“ForwR –
RevR” –
Forward start rising edge
–
Reverse start rising edge
DIN1: closed contact = start forward
(Rising edge required to start)
DIN2: closed contact = start reverse
(Rising edge required to start)
6
“StartR
-
Rev”
- Start command rising edge
–
Direction command
DIN1: closed contact = start
(Rising edge required to start)
open contact = stop
DIN2: closed contact = reverse
open contact = forward
7
“StrtR
-
Enable” –
Start command rising edge
–
Run Enable
DIN1: closed contact = start
(Rising edge required to start)
open contact = stop
DIN2: closed contact = start enabled
open contact = start disabled and drive stopped if running
8
“
RPuls-RPuls
” –
Start rising edge
–
Stop rising edge
DIN1: closed contact = Start
(Rising edge required to start)
DIN2: closed contact = Stop
(Rising edge required to stop)