174
• VACON®
apfiff09 marine
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
P2.6.3.1
Torque Limit
ID609
“Torque Limit”
The general torque limit for both motoring and generator sides. This value is the final limit
for all scaling functions. This value should not be used for scaling but for maximum
safety limit because the ramp up rate function is ineffective when this parameter is
changed. Only the motoring side torque limit has a ramp up limiting function.
P2.6.3.2
Motoring Torque limit ID1287
“MotorTorqueLimit”
Motoring side torque limit. This limit value is used for all scaling functions and torque limit
ramp rate functions if activated.
P2.6.3.3
Generator Torque limit ID1288
“GenerTorqueLimit”
Generator side torque limit. This limit is used for all scaling functions generator side
torque limit is not included in ramp up rate function.
P2.6.3.4
Motoring Torque limit 1
ID1625
“Mot.TorqueLim 1”
Motoring side torque limit that is activated by digital input.
P2.6.3.5
Generator Torque limit 1
ID1627
“Gen. Torque Lim 1”
Generator side torque limit that is activated by digital input.
Q1
Motoring
Q2 Generating
Q3
Motoring
Q4 Generating
T
ω
Positive torque limit
Motoring torque limit
Negative torque limit
Motoring torque limit
Generator torque limit
Generator torque limit