B04: FALSE = Reset Ramp Generator, TRUE = Enable Ramp Generator
This bit has priority over B05 and B06 in Control Word.
Reset Ramp Generator
: Closed Loop: Ramp generator is forced to zero, and the drive will make a
stop as fast as possible running against the set torque limits or, for example, overvoltage controller.
Enable Ramp Generator
: Ramp Generator function is enabled.
To activate Jogging function from fieldbus B04, B05 and B06 needs to be zero.
B05: FALSE = Freeze Ramp Generator, TRUE = Unfreeze Ramp Generator
This bit has priority over B06 but not over B05.
Freeze Ramp Generator:
Drive will not accept new reference from Fieldbus, drive remains at the
same speed.
Unfreeze Ramp Generator
: Drive will follower reference from Fieldbus.
To activate Jogging function from fieldbus B04, B05 and B06 needs to be zero.
B06: FALSE = Disable Set point, TRUE = Enable Set point
This bit has lowers priority compared to B04 and B05.
Disable Set point
: Reference (FW:FreqRef1) is forced to zero, and the drive will ramp to zero speed
Enable Set point
: Drive will follow reference.
To activate Jogging function from fieldbus B04, B05 and B06 needs to be zero.
B07: FALSE = No significance, TRUE = Fault Acknowledge
Fault Acknowledge
: The group signal is acknowledged with a positive edge; the drive reaction to a
fault depends on the type of fault (refer to "alarm handling in Appendix A.8). If the fault reaction has
isolated the voltage, the drive then goes into the "Switching On Inhibited" condition.
10.1.2.3 Jogging function
I/O Jogging Command
: Jogging function will start the drive to reference without additional start
command regardless of control place when given from IO. Jogging function requires enabling from
digital input before command is accepted. Inching is also disabled if there is a start command active
from active control place. If both inching references are active at the same time, the drive will stop.
Fieldbus Jogging Command
: Jogging command is activated by giving normal start command but
the ramp control bits CW.B4, B5 & B6 needs to be zero. Drive needs to be at zero speed before
command is accepted and CW.B4, B5 & B6 are active after drive is at zero speed when jogging
function is stopped.
RunRequest
Running
SR
SET
RESET
AND
IN 1
IN 2
NOT
IN
NOT
IN
NOT
IN
IO Enable Inching
AND
IN 1
IN 2
AND
IN 1
IN 2
OR
IN 1
IN 2
R_TRIG
IN
AND
IN 1
IN 2
IN 3
IN 4
Running
NOT
IN
SR
SET
RESET
Inching Active (Start)
OR
IN 1
IN 2
IN 3
IN 4
NOT
IN
AND
IN 1
IN 2
Running
Ready
NOT
IN
NOT
IN
SEL
OUT
DIG IN
DI
Enable Jogging
SEL
OUT
DIG IN
DI
Jogging Ref 1
SEL
OUT
DIG IN
DI
Jogging Ref 2
OR
IN 1
IN 2
OR
IN 1
IN 2
FB
FB Control Word.B8
FB
FB Control Word.B9
AND
IN 1
IN 2
IN 3
AND
IN 1
IN 2
IN 3
NOT
IN
NOT
IN
NOT
IN
FB
FB Control Word.B4
FB
FB Control Word.B5
FB
FB Control Word.B6
NOT
IN
RunRequest
NOT
IN
Enable Inching
SEL
G
IN 0
IN 1
FB Enable Inching
FB Enable Inching
FB Enable Inching
Summary of Contents for apfiff09 marine
Page 1: ...vacon nx ac drives apfiff09 marine application manual ...
Page 2: ......
Page 310: ......