288
• VACON®
apfiff09 marine
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
10.1.2.2 FB Control Word
FB Control Word ID1160
Signal
Comment
b0
ON
0>1 will reset the Switch On Inhibit state and bring the
drive to Ready Run. Should be reset after fault, Coast
Stop (b1) and Emergency Stop (b2) .
b1
Coasting Stop
0=Coast stop Active
1=Coast stop NOT active
b2
Quick Stop
0=Quick stop Active
1=Quick stop NOT active
b3
Start
Normal start command
0=Stop the drive
1=Start the drive
b4
Ramp Output to Zero
0=Force speed ramp output to zero
1=Release speed ramp output
b5
Ramp Hold
0=Hold speed ramp output
1=Release speed ramp
b6
Ramp Input to Zero
0=Force speed ramp input to zero
1=Release speed ramp input
b7
Fault Reset
0=No Action
1=Reset active faults
b8
Inching 1
Run the drive with defined constant speed
0=No Action
1=Run with constant speed
b9
Inching 2
Run the drive with defined constant speed
0=No Action
1=Run with constant speed
b10 Fieldbus Control Enable
Activate Fieldbus control when P3.1 =3/Fieldbus
0=Fieldbus Control NOT active
1=Activate Fieldbus Control
b11 Watch Dog
0>1>0>1…1 sec square wave clock. This is used to
check data communication between Profibus master and
the drive. Used to generate FB Communication -Fault.
b12
b13
b14
b15
B00: FALSE = OFF 1, TRUE = ON 1
OFF 1:
Drive will make
ramping stop and goes to “Ready to switch
-
on”
. If the
drive is in “Switch on
Inhibit” state
, this bit is used to reset this status.
ON:
Voltage connected to drive and/or DC link charged if drive has the control.
B01: FALSE = Coast stop (OFF 2), TRUE = ON 2
Coast Stop
: Drive will make coasting stop and goes to “Switch
-
on Inhibit” state
ON 2
: No Coast Stop command
B02: FALSE = Quick Stop (OFF 3), TRUE = ON 3
Quick Stop
: Drive will make stop function defined by Quick Stop function parameter.
ON 3
: No Quick stop command.
B03: FALSE = Stop Request, TRUE = Start Request
Stop Request
: Drive will make stop defined by stop function.
Start Request
: Start Command to the drive.