10.1.2.4 FB Status Word
FB Status Word ID65
Signal
Comment
b0
Ready to switch On
0=The drive NOT ready to switch ON
1=The drive is ready to switch ON
b1
Ready to Operate
0=The drive is NOT ready to run
1=The drive is ready to run
b2
Running
0=The drive is NOT running
1=The drive is running and ready to release the reference
b3
Fault Active
0=No fault active
1=Fault IS active
b4
Cost Stop NOT active
0=Coast stop active
1=Coast stop NOT active
b5
EM Stop not Active
0=Emergency stop active
1=Emergency stop NOT active
b6
Switch On Inhibit
0=No Inhibit
1=The drive is out of fault and coast / emergency stop
state.
b7
Warning
0=NO alarm
1=Alarm IS active
b8
Speed At Ref
0=Speed actual is NOT equal to speed reference
1=Speed actual is equal to speed reference
b9
FB Control Active
0=Fieldbus Control NOT active
1=Fieldbus Control active
b10 Above Limit
Indicate if speed actual is below the limit P2.4.16
0=Speed actual is below the speed limit
1=Speed actual is above the speed limit
b11
b12
b13
b14
b15 Watch Dog Feedback
B00: FALSE = Not Ready to Switch On, TRUE = Ready to Switch On
Not Ready to Switch On
:
Ready to Switch On
: Power supply is switched on, electronics initialized, main
contactor, if available, has dropped out, pulses are inhibited.
B01: FALSE = Not Ready To Operate, TRUE = Ready To Operate
Not Ready To Operate:
Ready To Operate
:
B02: FALSE = Drive is not operating, TRUE = Drive is operational
Drive is not operating:
Drive is not run state (modulating)
Drive is operational
: Drive is in run state and modulating. Also rotor flux is ready and brake is
opened if feedback signal is used.
B03: FALSE = No Fault, TRUE = Fault Present
No Fault:
Drive is not on fault state.
Fault Present
: Drive is in fault state.