7.1
95-8533
6-1
Section 6
Specifications
note
For USCG Approved System specifications, refer
to Appendix D.
EQ300X CONTROLLER
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will
not cause damage to the equipment.
INPUT POwEr—
9 watts nominal, 12 watts maximum.
LON cOmmUNIcATION—
Digital communication, transformer isolated (78.5
kbps).
rS-485 cOmmUNIcATION—
MODBUS Master/Slave capability.
Digital communication, transformer isolated (up to 115
kbps).
rS-232 cOmmUNIcATION—
S3 configuration only.
Digital communication, optically isolated.
cONTrOLNET—
Digital communication, transformer isolated (5 Mbps).
SErIAL INTErfAcE bOArd—
RS-485 Communication
: MODBUS master/slave
capability, ground fault monitored.
Digital communication, transformer isolated (up to 230
kbps).
RS-232 Communication
: MODBUS master/slave or
S3 configuration capability.
Digital communication, non-isolated (up to 230 kbps).
RS-232 Communication
: MODBUS master/slave
capability.
Digital communication, non-isolated (up to 230 kbps).
High Speed Serial Link (HSSL)
: Port used only for
redundant controller to controller communication.
UNSUPErVISEd OUTPUTS—
Dry Contact Rating: 1 ampere at 30 vdc maximum.
SPDT normally open/normally closed contact,
Configurable for normally energized or de-energized
(de-energized is the default mode).
UNSUPErVISEd INPUTS—
Two State input (on/off).
User selectable normally open or normally closed
contact (N.O. is the default).
TrOUbLE OUTPUT—
SPDT normally open/normally closed contact,
Non-Configurable, normally energized only.
TEmPErATUrE rANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage:
–40°F to +185°F (–40°C to +85°C).
Excluding communication port optional modules.
HUmIdITY rANGE—
5 to 95% RH, non-condensing.
VIbrATION—
FM 3260, FM 6310/6320.
dImENSIONS—
See Figure 6-1.
SHIPPING wEIGHT—
5 pounds (2.3 kilograms).
cErTIfIcATION—
FM / CSA:
Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
Performance verified.
Refer to Appendix A for FM Approval details, including
Protected Premises Fire Alarm Systems and EQP
Supervising Systems.
Refer to Appendix B for CSA Certification details.
Refer to Appendix D for USCG Approval details.
CENELEC/CE: ATEX/EMC Directive Compliant.
Performance verified per EN 61779-4.
0539
FM
®
II 3 G
EEx nC IIC T4
DEMKO 02 ATEX 133867U
T4 (Tamb = –40°C to +85°C).
Refer to Appendix C for CE Mark details.
Special conditions for safe use:
The device shall be installed in an enclosure that
complies with all relevant requirements of EN 50021:
1999, and provides a degree of ingress protection of
at least IP54. The device may only be installed,
connected or removed when the area is known to be
non-hazardous.
Summary of Contents for DET-TRONICS 95-8533
Page 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Page 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Page 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Page 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Page 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Page 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Page 143: ...APPENDIX E E 1 95 8533 7 1 ...