7.1
95-8533
6-9
SUPERVISED OUTPUT RATING—SIGNALING
TyPE, STyLE "y" - CHANNEL 6
mAXImUm OUTPUT cUrrENT—
2 amperes at 30 Vdc maximum, 15 Amp inrush.
Automatic short circuit protection provided.
SUPErVISOrY cUrrENT—
Reverse current monitored at 1.5 mA, ± 0.5 mA.
End of Line Resistor 10 K ohms ±20%.
rESPONSE TImE—
Output actuates in <0.15 second after acknowledging
an alarm command message.
SIGNALING OUTPUT, TYPES—
Configurable for device applications:
STANdArd “SAm” SELEcTIONS—
Continuous
60 beats per minute
120 beats per minute
Temporal Pattern.
Trouble
Supervisory
SUPERVISED OUTPUT RATING— RELEASING
TyPE - CHANNEL 7 AND 8
mAXImUm OUTPUT cUrrENT—
2 amperes at 30 Vdc maximum, 15 Amp inrush.
Automatic short circuit protection provided.
SUPErVISOrY cUrrENT—
Monitored at 1.3 mA ±0.2 mA.
No EOL resistor required.
rESPONSE TImE—
Output actuates in <0.15 second after acknowledging
an alarm command message.
rELEASING OUTPUT, TYPES—
Configurable for device applications:
– Continuous
– Timed.
EQ21XXPS POWER SUPPLIES
INPUT VOLTAGE—
Selectable for 120, 208 or 240 vac input power,
±10%.
INPUT cUrrENT—
60 Hz Models:
EQ2110PS: 4 amps at 120 VAC
EQ2130PS: 11 / 6 / 6 amps at 120 / 208 / 240 VAC
EQ2175PS: 24 / 15 / 12 amps at 120 / 208 / 240 VAC.
50 Hz Models:
EQ2111PS: 4 amps at 120 VAC
EQ2131PS: 6 amps at 240 VAC
EQ2176PS: 12 amps at 240 VAC.
OUTPUT cUrrENT—
EQ2110PS / EQ2111PS:
10 amperes at 24 VDC
EQ2130PS / EQ2131PS:
30 amperes at 24 VDC
EQ2175PS / EQ2176PS:
75 amperes at 24 VDC.
POwEr cONSUmPTION—
EQ2110PS / EQ2111PS:
46 Watts
EQ2130PS / EQ2131PS:
140 Watts
EQ2175PS / EQ2176PS:
349 Watts.
TEmPErATUrE rANGE—
Operating: +32°F to +122°F (0°C to +50°C)
Storage:
-40°F to +185°F (-40°C to +85°C).
HUmIdITY rANGE—
5 to 95% RH, non-condensing.
dImENSIONS—
in Inches (centimeters)
width
Height
depth
EQ211xPS:
19 (48.3)
7 (17.8)
15 (38.1)
EQ213xPS:
19 (48.3) 14 (35.6)
15 (38.1)
EQ217xPS:
19 (48.3) 14 (35.6)
15 (38.1)
note
Power supplies are designed for mounting in a
standard 19 inch rack. optional mounting
hardware is available for floor or wall mount
applications.
cErTIfIcATION—
FM / CSA: Ordinary locations.
Summary of Contents for DET-TRONICS 95-8533
Page 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Page 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Page 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Page 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Page 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Page 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Page 143: ...APPENDIX E E 1 95 8533 7 1 ...