3-13
7.1
95-8533
1
2
3
4
5
6
7
8
9
10
IDCSC
MANUAL PULL STATION
OR OTHER CONTACT DEVICE
14
13
12
11
–
–
+
+
24 VDC
+
–
+
–
A
B
A
B
CIRCUIT 1
CIRCUIT 2
COM 2
COM SHIELDS
COM 1
C2076
EOL (10K)
3.3 K
EOL (10K)
3.3 K
Figure 3-7—IDCSC Terminal Identification
EQ300X CONTROLLER
INSTALLATION
The following paragraphs describe how to properly
install and configure the EQ300X Controller.
ENCLOSURE REQUIREMENTS
The Controller must be properly installed in a suitable
enclosure that is rated for the location. The enclosure
must provide space to install and wire the Controller
and must also provide for ground wire termination.
The enclosure must contain either a keyed lock or a
special tool to gain access into the enclosure. The
enclosure should be rated for the temperature range
of the location plus the temperature rise of all
equipment installed inside the enclosure. The
enclosure must be rated for electrical equipment that
is going to be installed.
NOTe
The Controller and enclosure must be connected
to earth ground.
For ordinary locations when entry is required to
operate the equipment, the cabinet should be a dead-
front construction and 16-gauge cold-rolled steel.
The door lock system shall accept different keys for
entry. An Authorized Persons key and a Person-in-
charge key will allow entry into the cabinet. The
cabinet should contain a window to view the
Controller’s text display and LED indicators.
NOTe
For any selected enclosure, the enclosure must
conform to all applicable regulations and
requirements.
NOTe
The Trouble signal must be located in an area
where it is likely to be heard.
Classified locations require the appropriate hazardous
rated enclosure. It is recommended that operators/
switches be installed in the enclosure. This avoids
the need to declassify the area in order to operate the
Controller. Regulations require that key switches be
installed for certain operations. An appropriate
window should be part of the enclosure in order to
allow an operator to view the text display and LED
indicators.
NOTe
If an enclosure does not have a keyed entry, a
special tool is required to gain entry into an
enclosure.
Det-Tronics offers several approved (FM/CSA/
CENELEC/CE) hazardous area enclosures that have
Eagle Quantum Premier equipment installed in the
enclosure. Contact Det-Tronics for further information.
MOUNTING
The Controller is designed for direct panel mounting
or DIN rail (optional) mounting. See “Specifications”
section of this manual for mounting dimensions.
NOTe
Clips for DIN rail mounting are available, but
must be specified at the time of ordering.
NOTe
A minimum clearance of 4 inches between the
Controller and nearby equipment is required to
provide room for wiring and ventilation.
SERIAL INTERFACE BOARD
An optional Serial Interface Board is available for the
EQP Controller. See Figures 3-8 and 3-9 for details on
the electrical connections.
Summary of Contents for DET-TRONICS 95-8533
Page 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Page 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Page 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Page 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Page 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Page 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Page 143: ...APPENDIX E E 1 95 8533 7 1 ...