7.1
95-8533
6-7
EQ3710AIM ANALOG INPUT MODULE
POwEr rEQUIrEmENTS—
Module power consumption: 6 watts.
When supplying power to three-wire transmitters:
Maximum current at power input: 7.4 amperes.
Output current: 900 mA per channel maximum.
INPUT/OUTPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will
not cause damage to the equipment.
TEmPErATUrE rANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage: –67°F to +185°F (–55°C to +85°C).
HUmIdITY rANGE—
0 to 95% RH, non-condensing.
cHANNEL AccUrAcY—
Zero: ±0.3% full scale from –40°C to +85°C.
Span: ±0.5% full scale from –40°C to +85°C.
rESPONSE TImE—
1 to 100 LON devices:
< 2 seconds
101 to 200 LON devices: < 3 seconds
201 to 246 LON devices: < 4 seconds.
LON cOmmUNIcATION—
Digital communication, transformer isolated (78.5
kbps).
dImENSIONS—
Refer to Figure 6-3.
SHIPPING wEIGHT—
1 pound (0.45 kilograms).
cErTIfIcATION—
FM / CSA:
Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
CENELEC/CE: ATEX/EMC Directive Compliant.
0539
FM
®
II 3 G
EEx nC IIC T4
DEMKO 03 ATEX 136207U
T4 (Tamb = –40°C to +85°C).
Special conditions for safe use:
The device shall be installed in an enclosure that
complies with all relevant requirements of EN 50021:
1999, and provides a degree of ingress protection of
at least IP54. The device may only be installed,
connected or removed when the area is known to be
non-hazardous.
Refer to Appendix D for USCG Approval details.
HART INTERFACE MODULE (HIM)
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will
not cause damage to the equipment.
INPUT POwEr—
1.0 watt maximum.
INPUT/OUTPUT cUrrENT—
Operating: 4 -20 mA.
Maximum: 0-30 mA.
TEmPErATUrE rANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage:
–-67°F to +185°F (–55°C to +85°C).
HUmIdITY rANGE—
5 to 95% RH, non-condensing.
dImENSIONS—
See Figure 6-2.
SHIPPING wEIGHT—
0.5 pounds (0.2 kilograms)
cErTIfIcATION—
FM / CSA:
Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4 ).
CENELEC/CE: ATEX/EMC Directive Compliant.
0539
FM
®
II 3 G
EEx nA II T4
DEMKO 04 ATEX 136507U
T4 (Tamb = –40°C to +85°C).
Special conditions for Safe Use:
The HIM shall be installed in an enclosure that
complies with all relevant requirements of
EN50021:1999 and provides a degree of ingress
protection of at least IP54.
The HIM may only be installed, connected, or
removed when the area is known to be non-
hazardous.
Summary of Contents for DET-TRONICS 95-8533
Page 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Page 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Page 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Page 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Page 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Page 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Page 143: ...APPENDIX E E 1 95 8533 7 1 ...