95-8533
7.1
D-1
APPENDIX D
EAglE QuANtum PrEmIEr SyStEm
mArINE APPlICAtIONS
u.S. COASt guArD APPrOVAl NumbEr 161.002/49/0
Approved SyStem deScription
Refer to Table D-1 for a complete list of USCG approved equipment.
equip. no.
equipment type
manufacturer
Series/model description
1
EQ300X Controller
Det-Tronics
EQ3001P N(C) N(S) W(T)-C, panel mount only;
installed inside Rittal cabinet or equivalent NEMA 12
enclosure in controlled environments.
2
EQ3710AIM
Analog Input Module
Det-Tronics
EQ3710D(P) W, installed inside Rittal cabinet or
equivalent NEMA 12 enclosure in controlled environments;
NEMA 4X enclosure for open area installations.
3
EQ3720RM
Relay Module
Det-Tronics
EQ3720D(P) W, installed inside Rittal cabinet or
equivalent NEMA 12 enclosure in controlled environments;
NEMA 4X enclosure for open area installations.
4
EQ3730EDIO
Enhanced Discrete
Input/Output Module
Det-Tronics
EQ3730D(P) W(T); installed inside Rittal cabinet or
equivalent NEMA 12 enclosure in controlled environments;
NEMA 4X enclosure for open area installations.
5
EQ24xxNE Network
Extender Module
Det-Tronics
EQ245(6) 3NE;
Enclosure material: 5 – Aluminum, 6 –SS.
6
EQ22xxDCUEX Digital
Communication Unit,
Combustible
Det-Tronics
EQ225(6)3DCUEX;
Enclosure material: 5 – Aluminum, 6 –SS.
(Uses CGS Gas Sensor)
7
CGS Combustible Gas
Sensor
Det-Tronics
CGSS1A6C2R1X
(Used with the EQ22xxDCUEX)
8
PIRECLAx4
PointWatch Hydrocarbon
Gas Detector
Det-Tronics
PIRECLA (1) 4 A (B) 1 (2) W (T) 1 (2)
9
PIRECLAx4
PointWatch Hydrocar-
bon Gas Detector “Duct
Mount”
Det-Tronics
PIRECLA (1) 4 A (B) 1 (2) W (T) 1 (2);
with DEC Q900C1001 Duct Mount kit
10
X3301 Multispectrum
Flame Detector
Det-Tronics
X3301A (S) 4N (4M) 11 (13,14) W (T) 1 (2) ;
with Q9033A Al (Q9033B SS) swivel
11
STB Sensor
Termination Box
Det-Tronics
STB4 (5) A (S) 2N (2U, 3N, 5N, 6N) W
(Used with the Fenwal DAF Vertical Heat Detector)
12
EQ2220GFM Ground
Fault Monitor
Det-Tronics
EQ2220GFM is installed in the same enclosure
with EQ300X Controller
13
EQP2120PS-B
Power Supply
Phoenix Contact
(Germany)
Phoenix Model QUINT PS-100-240VAC/24VDC/20;
panel mount only, installed in the same enclosure
with EQ300X Controller
14
QUINT-DIODE/40Diode
Redundancy Module
Phoenix Contact
(Germany)
Phoenix QUINT-DIODE/40; panel mount only;
installed in the same enclosure with EQ300X Controller and
EQP2120PS-B Power supply
15
DAF Vertical Heat De-
tector
Kidde-Fenwal
(Fenwal)
Model 12-E27121-020-02; rated 140°F (60°C)
(Uses STB Sensor Termination Box)
Table D-1— List of Approved Equipment
Summary of Contents for DET-TRONICS 95-8533
Page 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Page 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Page 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Page 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Page 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Page 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Page 143: ...APPENDIX E E 1 95 8533 7 1 ...