7.1
95-8533
6-6
OUTPUT / NOTIFICATION / RELEASING CIRCUITS
UNSUPErVISEd OUTPUT rATING—
Short circuit protected: 2 amperes at 30 Vdc
maximum.
SUPErVISEd OUTPUT rATING—SIGNALING TYPE,
cLASS b, STYLE "Y".
mAXImUm OUTPUT cUrrENT—
2 amperes maximum, 15 Amp inrush.
Automatic short circuit protection provided.
SUPErVISOrY cUrrENT—
Reverse current monitored at 3.0 mA, ± 2.0mA.
rESPONSE TImE—
Output actuates in <0.15 second after acknowledging
an alarm command message.
EOL rESISTOrS—
10 K ohms ±2 K ohms.
SIGNALING OUTPUT, TYPES—
Configurable for device applications:
– Continuous
– 60 beats per second
– 120 beats per second
– Temporal Pattern.
note
All eight channels are synchronized when
programmed as a signaling output.
SUPErVISEd OUTPUT rATING— rELEASING
TYPE
mAXImUm OUTPUT cUrrENT—
2 amperes maximum, 15 Amp inrush.
Automatic short circuit protection provided.
SUPErVISOrY cUrrENT—
Monitored at 3.0 mA ±2.0 mA.
rESPONSE TImE—
Output actuates in <0.15 second after acknowledging
an alarm command message.
rELEASING OUTPUT, TYPES—
Configurable for device applications:
– Continuous
– Timed.
EQ3720 RELAY MODULE
POwEr rEQUIrEmENTS—
3 watts nominal, 4 watts maximum.
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will
not cause damage to the equipment.
rELAY cONTAcTS—
30 VDC, 2 amps resistive.
125 VAC, 0.5 amp resistive (FM and CSA only).
LON cOmmUNIcATION—
Digital communication, transformer isolated (78.5
kbps).
TEmPErATUrE rANGE—
Operating: –40°F to +185°F (–40°C to +85°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
HUmIdITY rANGE—
5 to 95% RH, non-condensing.
dImENSIONS—
Refer to Figure 6-3.
SHIPPING wEIGHT—
1 pound (0.45 kilograms).
cErTIfIcATION—
FM / CSA: Class I, Div. 2, Groups A, B, C, D (T4).
Class I, Zone 2, Group IIC (T4).
Refer to Appendix A for FM Approval details.
Refer to Appendix B for CSA Approval details.
Refer to Appendix D for USCG Approval details.
CENELEC/CE: ATEX/EMC Directive Compliant.
0539
FM
®
II 3 G
EEx nC IIC T4
DEMKO 03 ATEX 135246U
T4 (Tamb = –40°C to +85°C).
Vin = 24 vdc ±10%.
Refer to Appendix C for CE Mark details.
Special conditions for safe use:
The device shall be installed in an enclosure that
complies with all relevant requirements of EN 50021:
1999, and provides a degree of ingress protection of
at least IP54. The device may only be installed,
connected or removed when the area is known to be
non-hazardous.
rESPONSE TImE—
Actuates in <0.15 second after acknowledging an
alarm command message.
Summary of Contents for DET-TRONICS 95-8533
Page 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Page 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Page 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Page 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Page 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Page 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...