7.1
95-8533
4-8
8. ControlNet communication continues.
9. Text display’s first line indicates "*** Program
Mode ***"
10. Text display’s third line displays download status.
a) "Config Download" indicates the serial transfer
into memory from the PC to the Controller.
b) "Erasing Flash" indicates that the controller is
electronically erasing the contents of the Flash
memory.
c) "Writing to Flash" indicates that configuration
data stored in memory is being written down
into Flash memory.
d) "Flash Lock" indicates that the controller is
locking the configuration data into the Flash
memory.
Caution
the controller’s configuration data will be
corrupted if power is removed during a
download. Contact the factory if this occurs.
11. Initialize the RS-485 and configuration serial ports
with new parameters.
12. Initialized the ControlNet option board with new
parameters.
13. Enable static logic and user logic programs to
operate. The first scan program is run first.
14. Accept field device LON communications.
15. Poll the device type variable from LON field
devices.
16. Configure LON field devices.
17. Clear the Trouble condition.
18. Text display shows a normal operation marquee
message.
a) Text display’s first line indicates "Det-Tronics
Eagle Quantum Premier".
b) Text display’s third line displays time (24 hour
format) and date (month day/year).
Note
Depending on the condition of the LoN devices,
faults may persist for a number of minutes.
A and B
Cause
Action
Off
No power
None or power up.
Steady red
Faulted unit
Cycle power.
If fault persists, contact the factory.
Alternating red/green
Self-test
None
Alternating red/off
Incorrect node configuration
Check network address and other ControlNet configuration
parameters.
A or B
Cause
Action
Off
Channel disabled
Program network for redundant media, if required.
Steady green
Normal operation
None
Flashing green/off
Temporary errors
None; unit will self-correct.
Listen only
Cycle power.
Flashing red/off
Media fault
Check media for broken cables, loose connectors,
missing terminators, etc.
No other nodes present on network
Add other nodes to the network.
Flashing red/green
Incorrect network configuration
Cycle power or reset unit.
If fault persists, contact the factory.
Table 4-3—Status of ControlNet LED Indicators
Summary of Contents for DET-TRONICS 95-8533
Page 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Page 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Page 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Page 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Page 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Page 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Page 143: ...APPENDIX E E 1 95 8533 7 1 ...