7.1
3-8
95-8533
NETWORK AND NETWORK
EXTENDER INSTALLATION
Mounting
The device should be securely mounted to a vibration
free surface. (See the “Specifications” section in this
manual for device dimensions.)
Wiring
All devices on the LON are wired in a loop that starts
and ends at the System Controller. To ensure proper
operation, the LON should be wired using high speed
communication grade cable.
NOTe
Cable meeting the specifications listed in Table
3-6 is suitable for distances up to 2000 meters.
Any of the cable types listed in Table 3-7 can be used
for wiring the LON for the distances indicated.
NOTe
If no network extenders are used, the distances
listed are for the entire loop. If network extenders
are used, the distances listed are for the wiring
length between network extenders or between a
network extender and the System Controller.
Table 3-7—LON Maximum Cable Lengths
Note: *Use the same type of cable in each wiring segment
between network extenders.
**Maximum wire lengths represent the linear wire distance of
LON communications wiring between network extenders.
Be sure that selected cable meets all job specifications.
If necessary, consult factory for further suggested cable
types.
***Cables designed to ISA SP50 Type A or IEC 61158-2
Type A are suitable for use in LON/SLC wiring. For armored
version, contact cable manufacturer.
Table 3-6—Typical Specification for 16 AWG (1.5 mm
2
) LON Wiring Cable per Echelon
Minimum Typical Maximum
Units
Condition
DC Resistance, each conductor
14
14.7
15.5
ohm/km
20 C per ASTM D 4566
DC Resistance Unbalanced
5%
20 C per ASTM D 4566
Mutual Capacitance
55.9
nF/km
per ASTM D 4566
Characteristic Impedance
92
100
108
ohm
64 kHz to 1 MHz, per ASTM D 4566
Attenuation
20 kHz
1.3
dB/km
20 C per ASTM D 4566
64 kHz
1.9
78 kHz
2.2
156 kHz
3
256 kHz
4.8
512 kHz
8.1
772 kHz
11.3
1000 kHz
13.7
Propagation Delay
5.6
nsec/m
78 kHz
Length:
6,500 feet/2000 meters maximum (basic loop or between Network Extenders).
Type:
Single twisted pair.
Wire Gauge: 16 AWG, stranded (19 x 29), tinned copper with overall shield.
Cables meeting these specifications are good for up to 2000 meters.
T0049B
Length: 6,500 feet/2000 meters maximum (basic loop or between Network Extenders).
Type: Single twisted pair.
Wire Gauge: 16 AWG, stranded (19 x 29), tinned copper with overall shield.
Cables meeting these specifications are good for up to 2000 meters.
LON Cable
Maximum Length**
(Manufacturer and Part No.)*
Feet
Meters
Belden 8719
6,500
2,000
Belden 3073F (Tray Rated)
6,500
2,000
Det-Tronics NPLFP
6,500
2,000
Technor BFOU
4,900
1,500
Rockbestos Gardex Fieldbus***
1 Shielded Pair, 16 AWG,
Type TC, p/n FB02016-001
6,500
2,000
1 Shielded Pair, 18 AWG,
Type TC, p/n FB02018-001
6,500
2,000
Summary of Contents for DET-TRONICS 95-8533
Page 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Page 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Page 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Page 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Page 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Page 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Page 143: ...APPENDIX E E 1 95 8533 7 1 ...