5-4
Netra CT Server Service Manual • February 2007
TABLE 5-2
CompactPCI Board LED States and Meanings on the System Status Panel
Green
Power
LED state
Amber
Okay to
Remove
LED state
Meaning
Action
Off
Off
The slot is empty or the system
thinks that the slot is empty
because the system didn’t detect
the board when it was inserted.
If there is a board installed in this slot, then one of
the following is faulty:
• the board installed in the slot
• the alarm card
• the system controller board
Remove and replace the failed component to clear
this state.
Blinking
Off
The board is coming up or going
down.
Do not
remove the board in this state.
On
Off
The board is up and running.
Do not
remove the board in this state.
Off
On
The board is powered off.
You can remove the board in this state.
Blinking
On
The board is powered on, but it
is offline for some reason (for
example, a fault was detected on
the board).
Wait several seconds to see if the green Power LED
stops blinking. If it does not stop blinking after
several seconds, enter
cfgadm
and verify that the
board is in the
unconfigured
state, then perform
the necessary action, depending on the board:
• Alarm card—You can remove the alarm card in
this state.
• All other boards—Power off the slot through the
alarm card software, then remove the board.
On
On
The board is powered on and is
in use, but a fault has been
detected on the board.
Deactivate the board using one of the following
methods:
• Use the
cfgadm -f -c unconfigure
command
to deactivate the board. In some cases, this might
cause the system to panic, depending on the
nature of the board hardware or software.
• Halt the system and power off the slot through
the alarm card software, then remove the board.
The green Power LED gives status information:
• If the green Power LED goes off, remove the
board.
• If the green Power LED remains on, halt the
system and power off the slot through the alarm
card software.
Summary of Contents for Netra CT 410
Page 16: ...xvi Netra CT Server Service Manual February 2007...
Page 20: ...xx Netra CT Server Service Manual February 2007...
Page 28: ......
Page 44: ...2 10 Netra CT Server Service Manual February 2007...
Page 48: ...3 4 Netra CT Server Service Manual February 2007...
Page 49: ...PART 2 Troubleshooting the System Troubleshooting the System Chapter 4...
Page 50: ......
Page 88: ......
Page 98: ...5 10 Netra CT Server Service Manual February 2007...
Page 138: ...6 40 Netra CT Server Service Manual February 2007...
Page 154: ...7 16 Netra CT Server Service Manual February 2007...
Page 176: ...8 22 Netra CT Server Service Manual February 2007...
Page 178: ......
Page 198: ...10 10 Netra CT Server Service Manual February 2007...
Page 199: ...PART 5 Illustrated Parts List Illustrated Parts List Chapter 11...
Page 200: ......
Page 208: ...11 8 Netra CT Server Service Manual February 2007...
Page 210: ......
Page 265: ...Appendix A Connector Pinouts A 55...
Page 266: ...A 56 Netra CT Server Service Manual February 2007...
Page 288: ...D 4 Netra CT Server Service Manual February 2007...
Page 296: ...Index 4 Netra CT Server Service Manual February 2007 W web sites third party xxvi...