C-8
Netra CT Server Service Manual • February 2007
Cause
You rebooted the system with a failed board. The OpenBoot PROM has taken it out
of reset and probed it.
Action
The board is probably damaged and should not be used. Unconfigure the board
manually, and remove the board from the system using the instructions in
Chapter 6
.
Message
scsb#0: slot # Occupant configured, Regained HEALTHY#!
scsb#0: slot # Occupant Unconfigured, Regained HEALTHY#!
Cause
A CompactPCI board is sending conflicting HEALTHY and UNHEALTHY signals.
Action
The board has failed. Replace the I/O board using the instructions in
Chapter 6
.
Message
scsb#0: Successfully Downgraded to Basic Hotswap Mode
Cause
Basic
hot-swap was enabled on the system.
Action
No action is necessary.
Summary of Contents for Netra CT 410
Page 16: ...xvi Netra CT Server Service Manual February 2007...
Page 20: ...xx Netra CT Server Service Manual February 2007...
Page 28: ......
Page 44: ...2 10 Netra CT Server Service Manual February 2007...
Page 48: ...3 4 Netra CT Server Service Manual February 2007...
Page 49: ...PART 2 Troubleshooting the System Troubleshooting the System Chapter 4...
Page 50: ......
Page 88: ......
Page 98: ...5 10 Netra CT Server Service Manual February 2007...
Page 138: ...6 40 Netra CT Server Service Manual February 2007...
Page 154: ...7 16 Netra CT Server Service Manual February 2007...
Page 176: ...8 22 Netra CT Server Service Manual February 2007...
Page 178: ......
Page 198: ...10 10 Netra CT Server Service Manual February 2007...
Page 199: ...PART 5 Illustrated Parts List Illustrated Parts List Chapter 11...
Page 200: ......
Page 208: ...11 8 Netra CT Server Service Manual February 2007...
Page 210: ......
Page 265: ...Appendix A Connector Pinouts A 55...
Page 266: ...A 56 Netra CT Server Service Manual February 2007...
Page 288: ...D 4 Netra CT Server Service Manual February 2007...
Page 296: ...Index 4 Netra CT Server Service Manual February 2007 W web sites third party xxvi...