RA7000 and ESA10000 Storage Subsystems
4–12
EK–SMCPP–UG. A01
Table 4–4 EMU Fault Code LED Displays (continued)
Display
Error
Error Code 0D
Controller installed in expansion enclosure.
Master enclosure SCSI ID address incorrect.
Corrective Action
Complete first corrective action. If it does not correct the
problem, complete the second.
Install controller in master enclosure.
Change PVA SCSI ID to 0.
Error Code 0E
EMU memory test failed.
Correction Action
Replace EMU.
Controlled Power Shut
Down Display
Error Code 0F
Fewer than four operational power supplies.
Comment
The EMU initiates a controlled power shut down when
this condition occurs.
Corrective Action
See Chapter ? “Power Distribution” for detailed corrective
actions for this problem.
Error Code 10
EMU diagnostic program loaded.
Comment
The audible alarm is ON continuously and you cannot
clear it by pressing the alarm control switch.
Corrective Action
Complete first corrective action. If it does not correct the
problem, complete the second.
Load new microcode.
Replace EMU with one with the correct microcode.