EK–SMCPP–UG. A01
3–1
3
Configuring the Storage Cabinet
This chapter describes configuration rules and restrictions for configuring the
Environmental Monitor Unit. When specific rules and restrictions are not provided,
references are given to the proper StorageWorks documentation.
3.1
Configuring the Storage Cabinet
Configuring the storage cabinet is primarily configuring the EMU. Configuring
the EMU requires connecting the EMU communications bus and then using the
CLI SET_EMU command to establish the following:
•
Enclosure backplane temperature sensor set points on all enclosures
– SENSOR_1 or SENSOR_1_SETPOINT = DEFAULT
– SENSOR_2 or SENSOR_2_SETPOINT = DEFAULT
•
EMU module internal temperature sensor set point SENSOR_3 or
SENSOR_3_SETPOINT = DEFAULT
•
The blower speed controls of either FANSPEED = HIGH or FANSPEED =
AUTOMATIC
DIGITAL recommends setting the FANSPEED to AUTOMATIC, unless (1) the
ambient temperature is in excess of 38ºC (100ºF), (2) there is no air conditioning,
or both conditions exists. Should these conditions exist, DIGITAL recommends
setting the FAN SPEED to HIGH.
NOTE
For instructions on using these commands, refer
to the CLI Reference Manual.