The SIMODRIVE 611 feed modules with closed–loop control for the 1FT5 ser-
vomotors have an evaluation circuit, for the PTC thermistor integrated in the
motor winding.
The motors should be protected from inadmissibly high winding temperatures
with the monitoring combination (response temperature 150
°
C).
When the response temperature is reached, it is only signaled at the SIMO-
DRIVE 611 via an individual fault signal, terminals 289/294/296 and centrally via
terminals 5.1, 5.2 and 5.3 of the feed module as the drive should not intervene
directly in the machining process and disturb operation.
There is no internal system shutdown function to protect the motor. The user
must ensure that the motor can thermally recover immediately after the
temperature signal is output, by appropriately designing the adaptation
control. It may be necessary to shut down the motor immediately.
A delay time is not permissible.
If the motor is not thermally monitored, then the complete drive could be
destroyed if an overload condition occurs, or if the drive converter was
over–dimensioned.
Evaluation of the
motor PTC thermi-
stor for tempera-
ture monitoring
7.1.2 Interface overview, feed control, user–friendly interface
Summary of Contents for SIMODRIVE 611A
Page 2: ......
Page 6: ......
Page 7: ...SECTION 0 PRELIMINARY INFORMATION 0 7 ...
Page 8: ......
Page 17: ...Section 1 611A Analog Feed Drives 1 17 ...
Page 18: ...1 18 ...
Page 24: ...1 24 ...
Page 39: ...1 39 ...
Page 70: ...1 70 ...
Page 119: ...1 119 ...
Page 120: ......
Page 123: ......
Page 131: ......
Page 158: ...1 158 ...
Page 159: ...1 159 MOUNTING DIMENSIONS ...
Page 160: ...1 160 ...
Page 186: ......
Page 187: ...GENERAL INFORMATION REGARDING AC SERVO MOTORS AL S ...
Page 188: ......
Page 225: ...1FT5 AC SERVO MOTOR DESCRIPTIONS 1FT5 ...
Page 226: ......
Page 321: ...FEEDBACK DEVICES FOR 1FT5 GE ...
Page 322: ......