SIMODRIVE 611 (PJ)
Line fuses, commutating reactors, transformers and
main switch
Assignment of the line fuses to the NE modules
Fuses must be used which are designed to protect the line supply feeder ca-
bles.
The following can be used: NH, D, DO with gL characteristics according to VDE
0636, VDE 0641. Without restricting the performance data of the NE modules,
we recommend the SIEMENS fuse types listed below.
Table 3-10
UE mo-
dule
5/10 kW
UE mo-
dule
10/25 kW
UE mo-
dule
28/50 kW
I/R mo-
dule
16/21 kW
I/R mo-
dule
36/47 kW
I/R mo-
dule
55/71 kW
I/R mo-
dule
80/104 kW
I/R module
120/156
KW
I
rated
fuse
16 A
25 A
80 A
35 A
80 A
125 A
160 A
2x80 A 1)
250 A
2x125 A 1)
I
fuse
0.2 s
>70 A
>100 A
>360 A
>180 A
>360 A
>450 A
>650 A
>865 A
I
fuse
4 s
>50 A
>80 A
>260 A
>130 A
>260 A
>350 A
>505 A
>675 A
I
fuse
10 s
>42 A
>65 A
>200 A
>100 A
>200 A
>250 A
>360 A
>480 A
I
fuse
240 s
>30 A
>40 A
>135 A
>60 A
>135 A
>200 A
>280 A
>380 A
Recommended SIEMENS fuse types
Rated
voltage
415 V
AC
16 A D01
Neoz./
B.No.
5SE2116
25 A D02
Neoz./
B.No.
5SE2125
35 A D02
Neoz./
B.No.
5SE2135
Rated
voltage
500 V
AC
16 A DII
Diazed/
B.No.
5SB261
25 A DII
Diazed/
B.No.
5SB281
80 A DIV
Diazed/
B.No.
5SC211
35 A DIII
Diazed/
B.No.
5SB411
80 A DIV
Diazed/
B.No.
5SC211
Rated
voltage
500 V
AC
16 A size
00 NH/
B.No.
3NA3805
25 A size
00 NH/
B.No.
3NA3810
80 A size
00 NH/
B.No.
3NA3824
35 A size
00 NH/
B.No.
3NA3814
80 A size
00 NH/
B.No.
3NA3824
125 A size
00 NH/
B.No.
3NA3832
160 A size
1 NH/
B.No.
3NA3136
250 A size 1
NH/B.No.
3NA3144
The fuses/m.c.b.s used must fulfill the conditions of the values in the tables.
Fuses/m.c.b.s with lower currents are not recommended when the NE modules
are partially utilized, as the maximum current can be drawn from the NE module
during transient operations.
The tabulated values must be compared with the values obtained from the cur-
rent–time characteristic of the fuse used. If the fuse currents from the current–
time characteristics for the specified times in the table, are always greater than
the tabulated values, then the fuse can be used.
The maximum fuse rating which can be used (I
rated
fuse) is specified by the
maximum cross–section which can be connected at the terminals.
1) For applications with filter modules (square–wave current filters)
3.4.1 Assignment of the line fuses to the NE modules
Summary of Contents for SIMODRIVE 611A
Page 2: ......
Page 6: ......
Page 7: ...SECTION 0 PRELIMINARY INFORMATION 0 7 ...
Page 8: ......
Page 17: ...Section 1 611A Analog Feed Drives 1 17 ...
Page 18: ...1 18 ...
Page 24: ...1 24 ...
Page 39: ...1 39 ...
Page 70: ...1 70 ...
Page 119: ...1 119 ...
Page 120: ......
Page 123: ......
Page 131: ......
Page 158: ...1 158 ...
Page 159: ...1 159 MOUNTING DIMENSIONS ...
Page 160: ...1 160 ...
Page 186: ......
Page 187: ...GENERAL INFORMATION REGARDING AC SERVO MOTORS AL S ...
Page 188: ......
Page 225: ...1FT5 AC SERVO MOTOR DESCRIPTIONS 1FT5 ...
Page 226: ......
Page 321: ...FEEDBACK DEVICES FOR 1FT5 GE ...
Page 322: ......