W - Test Point = Actual Motor Current
( 10V = I-max as set in S2(A1)-DIP; 2, 3, 4 & 5)
S5(A2)-DIP; 2, 3, 4 & 5)
M - Test Point = Common reference for all Test Points
T - Test Point = Current Command
X - Test Point = Actual Motor Speed
( 40.0 V
Tacho
: 10 V = Rated Speed )
( 16.5 V
Tacho
: 11 V = Rated Speed )
M - LED = Motor Fault; A - LED = Axis(Drive) Fault
- Motor to Drive Feed Back Cable - Speed Controller at Limit ( > 200ms )
- Tachometer
- Drive Heat Sink
Overtemperature
( > 90
o
C)
- Rotor Position Detector - Motor
Overemperature
( > 155
o
C + / - 5
o
C)
- I
2
T Monitoring Activated ( I-
rms
> 1.1 x I-rated )
- Motor to Drive Power Cable disconnected
NOTE: If
Both
lights are lit, the Feed Back Cable may be disconnected(motor end ?)
Siemens Energy & Automation
Machine Industry Business
6 / 10 / 96 A-5 de
Interface Drawing for ;
Date
Revision
Drawn by
611-A SERVO,
2 Axes,
STANDARD VERSION
6FX2003-0CE12
( Motor End )
6FC9348-7AT
( Drive End )
Wiring of Motor to Drive F/B Cable
Tacho
, Rotor Position & Thermistor
( suggested Wire Size AWG 22 or 24 )
NOTE
:
Motor to Drive connections
must be exactly as shown !
Connections for
Optional
(G45) Motor Mounted
Brake [24 VDC, + / - 10%; Current range 0.4 to 3.25
Amps., dependent on Motor / Brake size]. If not
used, all three (3) wires should be connected to
ground.
Tacho
R
Tacho
S
Tacho
T
Tacho
M
P15(RPG)
RPD R
RPD S
RPD T
M(
Grnd
.)
PTC
PTC
Page 2 / 3
11
12
7
6
8
4
3
1
2
5
9
10
Jumpers
Dummy Plug
If the Motor is
disconnected,
the Module
will not fault
if this plug
is installed
6FX2003-1CF12
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Test Points and Fault LED’s
( A1 & A2 )
W
M
T M
X A
Test
Points
LED’s
S1(A1) & S4(A2)
Tacho
Jumpers
( close only for motors
with 16.5 V
Tacho’s
)
6
6
S2(A1) & S5(A2)-DIP(NOTE:
Underlined = Factory setting)
10 Torque ( Current ) Mode( on ), Velocity Mode(
off
)
9
8
Current Loop
7
Gain
( Factory setting
off
)
6
5
4
Current
3
Limit
( Factory setting
off
)
2
1 Motor Rotation Direction
vs
. voltage polarity
@ terminals
X33*
- 56 & 14. ( Factory setting
on
)
6
(
on
)
8
7
6
5
4
3
2
1
S3(A1) & S6(A2)-DIP(NOTE:
Underlined = Factory setting )
Current Controller integrator active (
on
) or
not active( off )-(Torque / Current Mode only) .
Master(
off
) / Slave( on )
Ready(
off
) / Fault( on ) Selection
Speed Controller
Adaption
active(on )/ not active(
off
)
Current Command Smoothing active( on ) / not active (
off
)
Velocity Controller Smoothing active(on ) / not active (
off
)
Tachometer Smoothing active( on ) / not active (
off
)
Velocity Command Smoothing active( on ) / not active (
off
)
(
on
)
X
3
0
1
S1
A1
S4
A2
S3
A1
S2
A1
S5
A2
S6
A2
6 The
correct setting
of these Items ( 3 places)
must be verified
prior to motor operation. See
Installation
Guide
for correct settings.
( Front Panel )
(Component side view )
CAUTION:
Use
care while handling
to avoid damaging
components.
A1 = Axis 1
A2 = Axis 2
11
12
7
6
8
4
3
1
2
5
9
10
8
15
7
14
1
9
4
6
13
5
2
11
12
Note: For correct grounding of the Shield, this end
should be connected to the Connector Shell or to
the M5 screw hole in the top of the Module.
Wiring of Motor to Drive Power Cable
( Wire size dependent on Motor Type )
611-A AC SERVO
Feed Module
1 ( U )
2 ( V )
6 ( W )
5 ( BR2 )
4 ( BR )
U2
V2
W2
-
+
SECTION G
1-176
Summary of Contents for SIMODRIVE 611A
Page 2: ......
Page 6: ......
Page 7: ...SECTION 0 PRELIMINARY INFORMATION 0 7 ...
Page 8: ......
Page 17: ...Section 1 611A Analog Feed Drives 1 17 ...
Page 18: ...1 18 ...
Page 24: ...1 24 ...
Page 39: ...1 39 ...
Page 70: ...1 70 ...
Page 119: ...1 119 ...
Page 120: ......
Page 123: ......
Page 131: ......
Page 158: ...1 158 ...
Page 159: ...1 159 MOUNTING DIMENSIONS ...
Page 160: ...1 160 ...
Page 186: ......
Page 187: ...GENERAL INFORMATION REGARDING AC SERVO MOTORS AL S ...
Page 188: ......
Page 225: ...1FT5 AC SERVO MOTOR DESCRIPTIONS 1FT5 ...
Page 226: ......
Page 321: ...FEEDBACK DEVICES FOR 1FT5 GE ...
Page 322: ......