While an error image is being stored in the EPROM, it remains possible to operate the reader and
to control it from an automation system. Actions are delayed however since the storage of image
data in read-only memory can take a relatively long time.
Persistent storage of diagnostics entries
The following restrictions apply to storing diagnostics entries in the EPROM:
• The processing time of the currently acquired code increases by the time required to store the
diagnostics entries. The time required to store a diagnostics entry in the EPROM depends on
the ambient temperature:
– 25 ºC up to 1 ms
– 50 ºC up to 32 ms
• Operating the reader and controlling it from an automation system are possible, however
input is delayed.
Note
Connection via Ethernet or PROFINET: Longer storage times
The storage times shown above apply only when there is no connection via Ethernet or
PROFINET. If there is such a connection, storage times are longer and they increase relative
to the network load.
8.4.3
Security
Figure 8-13
Security
In the "Security" menu, a user with "Administrator" authorization can specify rights for the
different user roles (Standard, Service, User1).
Parameterization
8.4 Settings
SIMOCRANE CenSOR
104
Operating Instructions, 07/2021
Summary of Contents for 6GA7202-2AA10-1BF1
Page 2: ......
Page 8: ...Table of contents SIMOCRANE CenSOR 6 Operating Instructions 07 2021 ...
Page 10: ...Introduction SIMOCRANE CenSOR 8 Operating Instructions 07 2021 ...
Page 62: ...Commissioning 7 3 Setting up the camera SIMOCRANE CenSOR 60 Operating Instructions 07 2021 ...
Page 158: ...Appendix A 3 Standards and certifications SIMOCRANE CenSOR 156 Operating Instructions 07 2021 ...
Page 168: ...Index SIMOCRANE CenSOR 166 Operating Instructions 07 2021 ...