Parameter Description
Parameter Description
78
Modbus
Code
Item
Shihlin
Protocol
Code
Information Content and Functions
Modbus
Address
H03
Parameter read out
H00~H63 P.0~P.499; for the range and decimal
point, please refer to the parameter list.
Every parameter modbus address is the
16 band parameter number. For
example: the modbus address of P.138
is H008A.
H0000
|
H01F3
H06/H10
Parameter write in
H80~HE3
---
Write/read
Parameter
page change
Read
H7F
H0000
:
P.0~P.99
;
H0001
:
P.100~P.199
;
H0002
:
P.200~P.299
;
H0003
:
P.300~P.399
;
H0004
:
P.400~P.499
。
---
Write
HFF
● Parameter recovery description table
Data
content
P operating
Communication
Parameters
(Note)
except P.21, P.187~P.199,
P.292, P.293, P.300~P.309
and Communication
Parameter
Another
Parameters
Error
Code
H5A5A
P.999
o
o
x
x
H9966
P.998
o
o
o
x
H9696
Communication
999
x
o
x
x
H55AA
Communication
998
x
o
o
x
HA5A5
P.996
x
x
x
o
Note: Communication parameters include P.32, P.33, P.36, P.48~P.53, P.79, P.153 and P.154.