Introduction of Shihlin Inverter
Introduction of Inverter
21
Note: 1. For SS2-TYPE series of inverters, brake resistor is not included. For information related to braking
resistor, please refer to 3.6.3.
2. For information related to regenerative voltage, please refer to P.30 in Chapter 5.
3. +/P and -/N are the positive and negative terminals of the internal DC voltage of the inverter. In order to
strengthen the braking capability during deceleration, it is suggested to purchase an optional brake unit to
be mounted between ter/P and -/N. The brake unit can effectively dissipate the feedback energy
from the motor to the inverter when decelerating. In case there is any problem on purchasing the brake
unit, please feel free to contact us.
4. For safety and noise reduction, grounding terminals of inverter must to be well grounded. To avoid
electric shocks and fire accidents, external metal wire of electrical equipment should be short and thick,
and it should be connected to the special grounding terminals of inverter. If many of the inverters are
placed together, all inverters must be connected to the common ground. Please refer to the following
diagram and do not form s circuit between the grounding terminals.
Poor