Parameter Description
Parameter Description
50
Parameter
Factory Setting
Setting Range
Remarks
7
5s
(
3.7KW and below
)
0~360s
When P.21=0
10s
(
5.5KW
)
0~3600s
When P.21=1
8
5s
(
3.7KW and below
)
0~360s
When P.21=0
10s
(
5.5KW
)
0~3600s
When P.21=1
20
50Hz
1~650Hz
When P.189=1
60Hz
When P.189=0
21
0
0, 1
0
Minimum setting increment:0.01s
1
Minimum setting increment:0.1s
44
9999
0~360s
When P.21=0
0~3600s
When P.21=1
9999
Not chosen
45
9999
0~360s
When P.21=0
0~3600s
When P.21=1
9999
Not chosen
<Setting>
• If P.21=0, the minimum increment of acceleration/deceleration time
(
P.7, P.8, P.16, P.44, P.45, and
P.111~P.118
)
is 0.01 seconds.
• If P.21=1, the minimum increment of acceleration/deceleration time
(
P.7, P.8, P.16, P.44, P.45, and
P.111~P.118
)
is 0.1 seconds.
• If RT is on, the second function is valid. In this case, the running characteristics of the motor are
refer to as the second function.
• If P.44=9999 (the default value), all of the second function is disabled. In this case, even though RT
is on, the acceleration time is still the set value of P.7, and the deceleration time is still the set value
of P.8, the torque boost is still the set value of P.0, and the base frequency is still the set value of P.3.
• If P.44≠9999 and P.45=9999, the acceleration/deceleration time is the set value of P.44 when RT is
on.
• If P.44≠9999 and P.46=9999, the torque boost is the set value of P.0 when RT is on.
If P.44≠9999 and P.46≠9999, the torque boost is the set value of P.46 when RT is on.
• If P.44≠9999 and P.47=9999, the base frequency is the set value of P.3 when RT is on.
If P.44≠9999 and P.47≠9999, the base frequency is the set value of P.47 when RT is on.
Note: RT in this paragraph is referred to as the multi-function control terminals. Please refer to P.80~P.84, P.86 for
function selection and features and refer to Section 3.5 for wiring.