Parameter Description
Parameter Description
112
• When the value of P.122 is 1~8, it is the initialization section of the cycle running.
For example: When P.122=3, the inverter will run circularly from the third section to the eighth
section after it finishes the running from the first section to the eighth section.
When P.123=0, the acceleration time is determined by P.7, and the deceleration time is
determined by P.8.
When P.123=1, the acceleration time and deceleration time are both determined by
P.111~P.118.
2.
Manually operation circle mode
Wiring pattern for manually operation circle mode terminals
• Connect an impulse type switch between RL and SD.
• After turning on the power, set P.80=35 according to the terminal wiring. At this time, inverter is at
standby.
• The mode of operation is presented in the figure below:
Note: 1. The parameter P.100, P.101~P.108, P.111~P.118 and P.121~123 is only for programmed operation mode. In
the manually operation circle mode, the acceleration time is determined by P.7, and the deceleration time is
determined by P.8.
2. The inverter will run across most of the eight section, and the frequency is determined by P.131~P.138
3. When the frequency is set, the inverter will run standby in this section if any section is 0. It means that at
the third mode the value of P.131 is not 0. Like the figure above, no matter what are the values of P.137
and P.138, the inverter will stop when pressing the sixth switch.
4. The manually operation circle mode has a single rotation direction. It has nothing to do with P.121 and STF
or STR signal.