5.45 Operation Panel Monitoring Selection (P.110)
P.110 “Operation panel monitoring selection”
Parameter
Factory
Setting
Setting
Range
Remarks
110
0
0~4
0
When the inverter starts, the operation panel enters the
monitoring mode automatically, and the screen displays
the output frequency.
1
When the inverter starts, the screen of the operation panel
displays the target frequency.
2
When the inverter starts, the operation panel enters the
monitoring mode automatically, and the screen displays
the output frequency steady.
3
When the inverter starts, the operation panel enters the
monitoring mode automatically, and the screen displays
the current pressure and feedback pressure of the constant
pressure system (note).
4
When the inverter starts, the operation panel keeps the
previous mode.
Note: When P.110 = 3, the screen display shows two sections. A decimal point is used to separate the boundaries.
What is on the left is the target pressure of the constant pressure system and what is on the right is the
feedback pressure of the constant pressure system. As shown in this figure,
, 20 denotes
that the target pressure of the constant pressure system is 2.0kg/cm
2
; 30 denotes that the feedback pressure of
the constant pressure system is 3.0kg/cm
2
.
5.46 The selection of positive and reverse rotation dead time (P.119)
P.119 “The dead time of positive and reverse rotation”
● When the inverter is running and receive the reverse rotation command, the output frequency will
decrease to 0 in the process of switching from the current rotation direction to the opposite rotation
direction. The dead time of positive and reverse rotation is the waiting or holding time after the
output frequency decreases to 0.
Parameter
Factory
setting
Setting
range
Remarks
119
0
0~3000.0s
0
Without the function
1~3000
The waiting or holding time after the output
frequency decreases to 0 when the positive
and reverse rotation is switching.