Appendix 1 Parameter list
Parameter List
150
Parameter
number
Name
Setting range
Minimum
setting unit
Default value
User setting
value
Reference
page
P.38
The maximum operation
frequency (the target
frequency is set by the
input signal of terminal
2-5)
1~650Hz
0.01Hz
50Hz/60Hz
(Note)
P81
P.39
The maximum operation
frequency (the target
frequency is set by the
input signal of terminal
4-5)
1~650Hz
0.01Hz
50Hz/60Hz
(Note)
P85
P.40
Multi-function output
terminal pattern
0~12, 17,18
1
0
P86
P.41
Up-to-frequency
sensitivity
0~100%
0.1%
10%
P89
P.42
Output frequency
detection for forward
rotation
0~650Hz
0.01Hz
6Hz
P90
P.43
Output frequency
detection for reverse
rotation
0~650Hz, 9999
0.01Hz
9999
P90
P.44
The second acceleration
time
0~360.00s/
0~3600.0s,9999
0.01s/0.1s
9999
P49
P.45
The second deceleration
time
0~360.00s/
0~3600.0s,9999
0.01s/0.1s
9999
P49
P.46
The second torque boost
0~30%,9999
0.1%
9999
P45
P.47
The second base
frequency
0~650Hz, 9999
0.01Hz
9999
P47
P.48
Data length
0, 1
1
0
P62
P.49
Stop bit length
0, 1
1
0
P62
P.50
Parity check selection
0, 1, 2
1
0
P62
P.51
CR & LF selection
1, 2
1
1
P62