5.60 The Paver Function (P.226~P.228)
P.226 “The paver function selection”
P.227 “The limit time of positive rotation”
P.228 “The limit time of reverse rotation”
Parameter
Factory
Setting
Setting
Range
Remarks
226
0
0, 1
The paver function is valid when 1 is set and invalid when 0 is set.
227
0
0~3600s
The inverter will decelerate and stop when the inverter keep
positive running for more than the setting time of P.227. The
function is invalid when 0 is set.
228
0
0~3600s
The inverter will decelerate and stop when the inverter keep
reverse running for more than the setting time of P.228. The
function is invalid when 0 is set.
<Setting>
The system wiring diagram
• Please wire as above diagram. Connect travel switch between M0 and SD, and between M1 and
SD.Connect pulse switch between STF and SD, and STR and SD.
• After the inverter is powered on and P.998 is performed, the paver system is selected when P.226 is
set to 1. The set values of multi-function terminals are all the factory default values which need
not to be changed. If the target frequency is given by the exterminal terminals, the closing of the
terminal M0 and M1will affect the target requency, so please set the value of P.5 and P.6 as the
same as the target frequency value.
• When K3 and K4 are all open, after pressing K1 it will forward rotate until K3 closes in a minute,
then contrarotate until K4 closes in a minute, and then forward rotate again to reciprocate. If K2
is pressed, the system will stop.
• When K3 (or K4) is closed, after pressing K1 it will contrarotate (or forward rotate) until K4 (or K3)
closes in a minute, and then forward rotate (or contrarotate). If K2 is pressed, the system will
stop.