Parameter Description
Parameter Description
117
Parameter
Factory
Setting
Setting
Range
Remarks
161
0
0~13,
19~21
4
The current feedback pressure of the constant pressure
system.
5
The current operation frequency.
6
The current electronic thermal accumulation rate.
7
The value of the input signal across terminal 2-5 (V).
8
The value of the input signal across terminal 4-5 (mA/V).
9
The output power(kW)
10
Reserved
11
Operating condition
,
and
12
The current inverter module temperature.
13
The current electronic thermal accumulation rate of motor.
19
External terminal input state(about the sort of terminal,
please refer to the table of the special monitor code in the
communication part)
20
External terminal output state(about the sort of terminal,
please refer to the table of the special monitor code in the
communication part)
21
The current valid carrier
5.53 PID Control (P.170~P.183, P.223~P.225)
P.170 “PID function selection”
P.171 “PID feedback control method
selection”
P.172 “PID proportion Gain”
P.173 “PID integration Gain”
P.174 “PID differential Gain”
P.175 “Abnormal deviation level”
P.176 “Exception duration time”
P.177 “Exception handling mode”
P.178 “Sleep detects deviation”
P.179 “Sleep detects duration time”
P.180 “Revival level”
P.181 “Outage level”
P.182 “Integral upper limit frequency”
P.183 “Deceleration step length with
stable pressure”
P.223 “Analog feedback bias pressure”
P.224 “Analog feedback gain pressure”
P.225 “Panel command”
● During the operation of PID control, the frequency displayed on the screen is the output frequency
of the inverter.
● The function of stall prevention operates according to the setting frequency before PID control.