Parameter Description
Parameter Description
94
5.26 The Choice of Locking Operation Keyboard Knob Setting (P.59)
P.59” The choice of locking operation keyboard knob setting”
Paramet
er
Factor
y
Settin
g
Setting Range
Remarks
59
0
0,1,10,11,100,101,110,111,200,201,210,211,1000,1001,1010,
1011,1100,1101,1110, 1111,1200,1201,1210,1211
---
• P.59 is set by the digits, and there are 4 digits in total. The meaning of each digit is as follows:
P.59 =
0
0
0
0
0, the default value, reserved
0, the jog dial has no set function
1, the jog dial has set function
0, when the frequency is changed, it will be saved automatically in 30s;
1, when the frequency is changed, it will be saved automatically in 10s;
2, when the frequency is changed, it won
’
t be saved automatically.
0, after the frequency is set by jog dial, the changed
frequency will be valid immediately;
1, after the frequency is set by jog dial, the changed
frequency will be valid after pressing the set key.
5.27 Input Signal Filter Constant (P.60)
P.60 “Input signal filter constant”
● When the running frequency is set by a voltage signal or a current signal, the voltage or current
signal would be processed by an AD converter. Due to the effect of device accuracy or noises, the
external voltage signal or current signal may fluctuate and as a result, the running frequency
fluctuates, too.
● Input signal filter constant setting P.60 is used to filter the fluctuation of the running frequency
caused by above factors. The larger the P.60 set value is, the better the filter performance is, but a
larger delay would be resulted in.
Parameter
Factory Setting
Setting Range
Remarks
60
31
0~31
---