Parameter Description
Parameter Description
110
5.43 The Second Frequency Source
(
P.97
)
P.97 “The second frequency source”
●When multi-function control terminal selects the second frequency source setting enable which is
valid, the frequency source is decided according to the P.97 setting value. And in this condition, it
is impossible to change the operation mode.
Parameter Factory Setting
Setting Range
Remarks
97
0
0~2
0
Frequency is given by operation panel PU
1
Frequency is given by communication
2
Frequency is given by external terminal
5.44 Programmed Operation Mode (P.100~P.108, P.111~P.118, P.121~P.123,
P.131~P.138)
P.100 “Minute/second selection”
P.101~P.108 “Runtime of each section”
P.111~P.118 “Acceleration/deceleration
time of each section”
P.121 “Run direction in each section”
P.122 “Cycle selection”
P.123 “Acceleration/deceleration time
setting selection”
P.131~P.138
“Frequency
of
each
section”
Note: About multi-function control terminals function-selection and description, please refer to P.80 ~ P.84
、
P.86
About its corresponding wire arrangement, please refer to section 3.5.6