5.74 Motor Parameter (P.302~P.309)
P.302 “Motor rated power”
P.303 “Motor poles”
P.304 “Motor rated voltage”
P.305 “Motor rated frequency”
P.306 “Motor rated current”
P.307 “Motor rated rotation speed”
P.308 “Motor excitation current”
P.309 “Stator resistance”
Parameter
Factory setting
Setting range
Remarks
302
0
0~160
---
303
4
0~8
---
304
220/440V
0~440V
---
305
50Hz
0~650Hz
P.189=1
60Hz
P.189=0
306
Horsepower-based
0~500A
---
307
1410 r/min
0~9998 r/min
P.189=1
1710 r/min
P.189=0
308
Horsepower-based
0~500A
---
309
Horsepower-based
99.98Ω
---
<Setting>
• When the motor can be fully separated from the load, select P.301=1. When the motor is running,
the motor parameter will carry out auto-tuning. Then press
FWD
or
REV
on the keyboard panel for the
inverter to automatically calculate the following parameter: P.308~P.309.
• When the motor cannot be fully separated from the load, select P.301=2. When the motor is stopped,
the motor parameter will carry out auto-tuning. Then press
FWD
or
REV
on the keyboard panel for the
inverter to automatically calculate the following parameter P.308~P.309.
• The users can use the motor's nameplate to calculate the idling current. The motor nameplate
parameters used in the calculation are: rated voltage U, rated current I, rated frequency
f
and power
factor
η
.
Idling current:
2
0
1
η
−
×
=
I
I
Note: 1. When the inverter is used with a motor of a different level, verify the input motor’s nameplate parameter
P.302~P.307. The vector control method is heavily dependent upon motor parameters. To achieve a good
control performance, the controlled motor’s correct parameters have to be acquired.
2. When any or many values of P.302~P.309 are manually revised, perform the function of P.997 to reload the
new values of the parameters.