Appendix 1 Parameter list
Parameter List
149
Parameter
number
Name
Setting range
Minimum
setting unit
Default value
User setting
value
Reference
page
P.19 Base
frequency
voltage
0~1000V, 9999
0.1V
9999
P47
P.20
Acceleration/deceleration
reference frequency
1~650Hz
0.01Hz
50Hz/60Hz
(Note)
P49
P.21
Acceleration/deceleration
time increments
0,1
1
0
P49
P.22
Stall prevention operation
level
0~250%
0.1%
200%
P56
P.23
Compensation factor at
level reduction
0~200%, 9999
0.1%
9999
P56
P.24
Speed 4
0~650Hz, 9999
0.01Hz
9999
P48
P.25 Speed 5
0~650Hz, 9999
0.01Hz
9999
P48
P.26 Speed 6
0~650Hz, 9999
0.01Hz
9999
P48
P.27 Speed 7
0~650Hz, 9999
0.01Hz
9999
P48
P.28
Output frequency filter
constant
0~31
1
0
P57
P.29
Acceleration/deceleration
curve selection
0~3
1
0
P58
P.30
Regenerative brake
function selection
0, 1
1
0
P61
P.31 Soft-PWM selection
0~2
1
0
P61
P.32
Serial communication
Baud rate selection
0~3
1
1
P62
P.33
Communication protocol
selection
0, 1
1
0
P62
P.34 Reserved
P.35
Communication Running
and Speed Command
Selection
0,1
1
0
P79
P.36 Inverter station number
0~254
1
0
P62
P.37 Speed display
0~5000.0r/min
0.1r/min
0 r/min
P80
0~9999r/min
1r/min