Parameter Description
Parameter Description
103
Para-
meter
Terminal
Factory
Setting
Setting
Range
Value Function Name
Function Description
Remarks
82
M2
4
0~41
,
43~45
8
RT
When RT is on, the
characteristics are the same
as the second function.
Please refer to
P.44
9
EXJ
(External JOG)
At the external mode, the
target frequency is set by
P.15 and the acceleration/
deceleration time is set by
P.16 when EXJ is on (Note
4).
83
STF
0
0~40
,
43~45
10
STF+EXJ
Multiplexed function
The
multiplexed
function is the
complex of
several basic
functions. It
means that one
multiplexed
terminal can
be used to
realize several
basic
functions.
11
STR+EXJ
12
STF+RT
13
STR+RT
14
STF+RL
15
STR+RL
16
STF+RM
17
STR+RM
18
STF+RH
19
STR+RH
20
STF+RL+RM
21
STR+RL+RM
22
STF+RT+RL
23
STR+RT+RL
24
STF+RT+RM
25
STR+RT+RM
26 STF+RT+RL+RM
27 STR+RT+RL+RM
84
STR
1
0~40
,
43~45
28
RUN
At the external mode, the
inverter runs when RUN is
on.
29
STF/STR
At the external mode, it is
used with RUN. The
inverter runs forwards when
STF/STR is on, and runs
reversely when STF/STR is
off.
Run forward
/reverse
control signal
30
RES
External Reset
31
STOP
At the external mode, it can
be used as a three-wire
mode with the RUN signal
or the STF/STR terminal
(note 4).
32
REX
Multi-speed