Parameter Description
Parameter Description
111
Parameter Factory Setting
Setting Range
Remarks
100
1
0, 1
0
The running time minimum increment is 1
minute.
1
The running time minimum increment is 1
second.
101~108
0s
0~6000s
---
111~118
0s
0~600s
When P.21=0
0~6000s
When P.21=1
Parameter Factory Setting
Setting Range
Remarks
121
0
0~225
0: Cycle function invalid;
1~8: Run circularly
122
0
0~8
---
123
0
0, 1
---
131~138
0Hz
0~650Hz
---
<Setting>
1. Programmed operation mode
• The calculation methods of runtime and acceleration/deceleration time in each section are presented
in the figure below:
• The run direction is set in binary form (8-bit), then translated to decimal form and stored in P.121.
‘1’ denotes run forward, and ‘0’ denotes run reverse. The highest bit is the run direction of section 8,
and the lowest bit is the direction of section 1.
For example: Suppose that section 1 for run forward, section 2 for run reverse, section 3 for run
reverse, section 4 for run forward, section 5 for run reverse, section 6 for run forward,
section 7 for run forward, and section 8 for run reverse, then the value in binary form
is 01101001:
P.121=0×27+1×26+1×25+0×24+1×23+0×22+0×21+1×20=105
• When P.122=0, it won’t run circularly.