Parameter Description
Parameter Description
46
5.2 Range of the Output Frequency (P.1, P.2, P.18)
P.1 “Maximum frequency”
P.2 “Minimum frequency”
P.18 “High-speed maximum
frequency”
● The upper limit and the lower limit of the output frequency can be restricted.
Parameter
Factory Setting
Setting Range
Remarks
1
120Hz
0~120Hz
---
2
0Hz
0~120Hz
---
18
120Hz
120~650Hz
---
<Setting>
• If the target frequency
≦
P.2, the steady output frequency = P.2.
• If P.2
<
target frequency
≦
P.1 (P.18), the steady output frequency = the target frequency.
• If P.1 (P.18)
<
target frequency, the steady output frequency = P.1.
Note: 1. The maximum frequency and the high-speed maximum frequency are interrelated. P.1 must be used (the
setting range of P.1 is 0~120Hz) if the target upper limit frequency is in the range of 0~120Hz. P.18 must
be used (the setting range of P.18 is 120~650Hz) if the target upper limit frequency is in the range of
120~650Hz.
2. If P.1
<
P.2, the steady output frequency will be clamped to P.1.
3. The set frequency value can not exceed the value of P.1.