Parameter Description
Parameter Description
77
Modbus
Code
Item
Shihlin
Protocol
Code
Information Content and Functions
Modbus
Address
H06/H10
Operati
on
frequen
cy
write in
EEPR
OM
HEE
H0000~HFDE8: 0~650HZ
H1009
RAM
HED
H1002
H06/H10
Inverter
parameter and
error code
erased.
HFC
See parameter recovery
description table
H5A5A
H1104
H9966
H1103
H9696
H1106
H55AA
H1105
HA5A5
H1102
H03
Monitor the
external
operation
condition
H7C
H0000~H000F:
H1012
H03
Monitor the INV
real-time data
---
The corresponding monitoring value of
each Modbus Address is as follows:
H1014: external terminal input state
H1015: external terminal output state
H1016: 2-5 terminal input voltage
H1017:
4-5
terminal
input
current/voltage
H1018: AM-5 terminal output voltage
H1019: DC bus voltage
H101A: rate of heat accumulated by
inverter electronic
H101B: inverter output power
H101C: rate of temperature rising
accumulated by inverter
H101D:
temperature
of
inverter
module
H101E: rate of the heat accumulated
by motor electronic
H101F: target pressure when PID
control
H1020: feedback pressure when PID
control
H1014
~
H1012