Parameter Description
Parameter Description
100
Note: The optimum carrier frequency shall be eight times greater than the target frequency.
5.33 Stop or Reset Function Selection (P.75
)
P.75 “Stop or reset function selection”
Parameter
Factory Setting
Setting Range
Remarks
75
1
0, 1
---
<Setting>
• When P.75=0, it is only suitable for the PU mode and the H2 mode (combined mode 2). Pressing
STOP
RESET
during running can stop the motor.
• When P.75=1, it is only suitable for the chosen mode. Press
STOP
RESET
during running can stop the motor.
Note: 1. When the alarm goes off, press
for 1 second to reset the inverter. In normal or abnormal conditions, the
reset can be executed by P.997.
2. There are two built-in programs for emulation thermal-accumulating relay: the electronic thermal relay
and the IGBT module thermal relay. Once reset occurs, the values of the two relay for the electronic
thermal relay and the IGBT module thermal relay will be set to zero.
3. In any modes other than the external mode or the H2 mode, the motor can be stopped by pressing
STOP
RESET
when P.75=1. The inverter would display E0, and all the functions of the inverter are disabled. It can
restart by:
(1). Terminate external STF/STR command (At the programmed operation mode, there’s no need to
terminate the start signal. The inverter will continue to run at the section where it stopped after
reset.)
(2). Press
STOP
RESET
for 1.0s.