74
MOVIDRIVE
®
MD_60A Operating Instructions
Fault messages and list of faults
54
No reference
travel
No
response
Only with DPx11A:
Reference travel not performed with "GO0" or
"SET0" command.
Perform reference travel.
55
Machine
parameters
No
response
Only with DPx11A:
Incorrect input of a machine parameter (e.g.
incorrect value range).
Check machine parameter and correct it.
56
Missing
required HW
No
response
Only with DPx11A:
User program addresses a hardware item
which is not fitted.
Correct user program or insert necessary
hardware into inverter.
57
No program
No
response
Only with DPx11A:
Attempt was made to call up a non-existent
user program.
•
Modify program call
•
Load program to be called into program
memory.
58
No record
number
No
response
Only with DPx11A:
Attempt was made to jump to a non-existent
record number in user program.
Correct user program.
59
No subroutine
No
response
Only with DPx11A:
Attempt was made to call up a non-existent
subroutine in user program.
•
Correct subroutine call in user program.
•
Make subroutine to be called available.
60
Target position
outside
No
response
Only with DPx11A:
Travel command was transmitted in user
program which targets a position outside travel
range.
•
Correct user program.
•
Adapt travel range.
61
Prog. speed
> Vmax
No
response
Only with DPx11A:
Speed entered in user program is faster than
maximum speed specified in machine
parameters.
•
Adapt travel speed in user program.
•
Adapt maximum speed in machine
parameters.
62
FLASH-
EPROM DPx
No
response
Only with DPx11A:
Fault during write access to flash-EPROM of
DPx11A.
Contact SEW Service for advice if this
reoccurs.
63
Division by
zero
No
response
Only with DPx11A:
Division by zero was performed in user
program using calculation operation SET Hxx/
Hyy.
Correct user program.
64
Subroutine
nesting
No
response
Only with DPx11A:
•
Maximum nesting depth for subroutines
reached.
•
Recursive subroutine call (program is
calling itself).
•
Alter program structure.
•
Correct user program.
65
LM628
command
No
response
Only with DPx11A:
Incorrect command to position controller
component.
Inform SEW Service if fault cannot be reset or
if it occurs frequently.
66
Prog.
memory full
No
response
Only with DPx11A:
Maximum capacity of program memory has
been exceeded.
•
Delete programs from program memory
that are no longer required.
•
If all programs in program memory are
needed then optimize program contents.
67
DPx remote
time
No
response
Only with DPx11A:
Communication interruption during PC-
controlled mode.
Check connection between PC and inverter.
68
Not at target
position
No
response
Only with DPx11A:
Specified target position was not reached
within 5 seconds.
•
P-component set too small.
•
Position window too small.
•
Drive has encountered obstacle.
•
Check setting of P-component and
position window and set larger values if
appropriate.
•
Check mechanical components can move
freely.
69
No feed
enable
No
response
Only with DPx11A:
No "Feed enable" signal at terminal X11:6.
Check wiring and signal level at terminal
X11:6.
Fault
code
Description
Reaction
P Possible cause
Measure