40
MOVIDRIVE
®
MD_60A Operating Instructions
Encoder and resolver connection
External
encoders
Only encoders with a signal level according to RS-422 (5 V-TTL) are allowed to be
connected to X14: of MOVIDRIVE
®
MDV/MDS units.
Voltage supply
Encoders with 24 V
DC
voltage supply (max. 180 mA) are connected directly to X14:.
These encoders are then powered by the inverter.
Encoders with a 5 V
DC
voltage supply must be connected via the "5 V encoder power
supply type DWI11A" option (part number 822 759 4).
Connection
External encoder with 24 V
DC
voltage supply:
Cut off the violet conductor (VT) of the cable at the encoder end.
External encoder with 5 V
DC
voltage supply:
* Connect the sensor line (VT) on the encoder to UB, do not jumper on the DWI11A!
03776AXX
Fig. 40: External encoder direct to X14:
03777AXX
Fig. 41: Connect via DWI11A
1
6
2
7
3
8
9
5
4
YE
GN
RD
BU
PK
GY
WH
BN
VT
5
1
9
6
MOVIDRIVE
X14:
®
max. 100 m (330 ft)
A (K1)
(
)
B (K2)
(
)
C (K0)
(
)
UB
A K1
B K2
C K0
⊥
ES1R / ES2R / EV1R
UB
K1 K2 K0
⊥
K1 K2 K0
y
y
UB
A B C
⊥
A B C
✂
1
5
5
1
6
9
9
6
DWI11A
X2:
Encoder
X1:
MO
VIDRIVE
max. 5 m (16.5 ft)
max. 100 m (330 ft)
5
1
9
6
ES1T / ES2T / EV1T
1
6
2
7
3
8
9
5
4*
y
y
YE
GN
RD
BU
PK
GY
WH
BN
VT*
1
6
2
7
3
8
9
5
4
A (K1)
(
)
B (K2)
(
)
C (K0)
(
)
UB
A K1
B K2
C K0
⊥
A (K1)
(
)
B (K2)
(
)
C (K0)
(
)
UB
N.C.
A K1
B K2
C K0
⊥
1
6
2
7
3
8
9
5
4
y
y
UB
K1 K2 K0
⊥
K1 K2 K0
UB
A B C
⊥
A B C
MOVIDRIVE
X14:
®