MOVIDRIVE
®
MD_60A Operating Instructions
87
MOVIDRIVE® MD_60A...-2_3 (230 V units)
Size 4
MOVIDRIVE
®
MD_60A
0220-203-4-0_
0300-203-4-0_
INPUT
Supply voltage
V
in
3
×
200 V
AC
-10 % – 3
×
240 V
AC
+10 %
Supply frequency
f
in
50 Hz – 60 Hz
±
5 %
Rated system current I
in
100 %
(at V
in
= 3
×
230 V
AC
)
125 %
72 A
AC
90 A
AC
86 A
AC
107 A
AC
OUTPUT
Output rated power
1)
P
N
(at V
in
= 3
×
200 – 240 V
AC
)
31.8 kVA
37.8 kVA
Output rated current
I
N
(at V
in
= 3
×
230 V
AC
)
80 A
AC
95 A
AC
Current limitation
I
max
Motor and regenerative 150 % I
N
, duration depending on the capacity utilization
Internal current limitation
I
max
= 0 – 150 % can be set in menu (P303 / P313)
Minimum permitted brake
R
BRmin
resistance value (4Q operation)
3.0
Ω
Output voltage
V
out
max. V
in
PWM frequency
f
PWM
Adjustable with VFC: 4/8/12/16 kHz (P860 / P861); with CFC/SERVO fixed at 8 kHz
Speed range / resolution
n
A
/
∆
n
A
-5000 – 0 – +5000 rpm / 0.2 rpm across the entire range
GENERAL
Power loss at P
N
P
Vmax
1100 W
1300 W
Cooling air consumption
180 m
3
/h (108 ft
3
/min)
Weight
27 kg (59.53 lb)
Dimensions
W
×
H
×
D
280
×
522
×
345 mm (11.02
×
20.55
×
13.58 in)
1) MDF and MDV units in VFC operating modes: The performance data apply to f
PWM
= 4 kHz (factory setting).
MDF60A standard type (VFC)
0220-203-4-00
0300-203-4-00
Part number
827 177 1
827 178 X
MDF60A technology type (VFC)
0220-203-4-0T
0300-203-4-0T
Part number
827 371 5
827 372 3
Constant load
Rec. motor power P
Mot
22 kW (30 HP)
30 kW (40 HP)
Variable torque load or constant
load without overload
Rec. motor power P
Mot
30 kW (40 HP)
37 kW (50 HP)
Continuous output current = 125 % I
N
I
D
(at V
in
= 3
×
230 V
AC
and f
PWM
= 4 kHz)
100 A
AC
118 A
AC
MDV60A standard type (VFC/CFC)
0220-203-4-00
0300-203-4-00
Part number
827 261 1
827 262 X
MDV60A technology type (VFC/CFC)
0220-203-4-0T
0300-203-4-0T
Part number
827 380 4
827 381 2
VFC operating mode
Recommended motor power
→
MDF60A
CFC operating mode
Continuous output current = 100 % I
N
I
D
80 A
AC
95 A
AC
Recommended motor power
→
System Manual, Sec. Project Planning, CFC motor selection
P
i
f
kVA
Hz
n
Summary of Contents for MOVIDRIVE MD*60A Series
Page 3: ...MOVIDRIVE MD_60A Edition 09 2001 Operating Instructions 1053 2617 EN ...
Page 4: ...SEW EURODRIVE ...
Page 100: ...10 2000 ...