MOVIDRIVE
®
MD_60A Operating Instructions
71
Fault messages and list of faults
6.3
Fault messages and list of faults
Fault message on
7-segment
display
The fault or warning code is displayed in BCD format. The following display sequence
is adhered to (e.g. fault code 84):
The display switches over to the operating display following a reset or if the fault or
warning code once more resumes the value "0".
List of faults
A dot in the "P" column means that the response is programmable (P83_ Fault
response). The factory set fault response is listed in the "Response" column.
01038AXX
Flashes, approx. 1 s
Display off, approx. 0.2 s
Tens, approx. 1 s
Display off, approx. 0.2 s
Ones, approx. 1 s
Display off, approx. 0.2 s
Fault
code
Description
Reaction
P Possible cause
Measure
00
No fault
-
01
Over-current
Immediate
shut-off
•
Short circuit on output
•
Motor too large
•
Defective output stage
•
Rectify the short circuit
•
Connect a smaller motor
•
Contact SEW Service for advice if the
output stage is defective
03
Ground fault
Immediate
shut-off
Ground fault
•
in the connecting harness
•
in the inverter
•
in the motor
•
Eliminate ground fault
•
Contact SEW Service for advice
04
Brake chopper
Immediate
switch-off
•
Regenerative power excessive
•
Braking resistor circuit interrupted
•
Short circuit in braking resistor circuit
•
Excessively high braking resistance
•
Brake chopper defective
•
Extend deceleration ramps
•
Check feeder to braking resistor
•
Check technical data of braking resistor
•
Fit a new MOVIDRIVE
®
if the brake
chopper is defective
07
DC link
overvoltage
Immediate
switch-off
DC link voltage too high
•
Extend deceleration ramps
•
Check connecting harness for braking
resistor
•
Check technical data of braking resistor