Installation instructions for basic unit
4
Installation
4.1
Installation instructions for basic unit
Tightening
torques
•
Only use genuine connection elements. Note the permitted tightening torques
of MOVIDRIVE
®
power terminals.
– Size 1
→
0.6 Nm (5.3 lb.in)
– Size 2
→
1.5 Nm (13.3 lb.in)
– Size 3
→
3.5 Nm (31 lb.in)
– Sizes 4 and 5
→
14 Nm (124 lb.in)
Minimum
clearance and
mounting
position
•
Leave 100 mm (4 in) clearance at the top and bottom for optimum cooling. No
lateral clearance required; the units can be lined up side-by-side. With sizes 4 and 5,
do not install any components which are sensitive to high temperatures within 300
mm (11.81 in) of the top of the unit. Only install the units vertically. You must not
install them horizontally, tilted or upside down.
It is essential to comply with the safety notes during installation!
02475AXX
Fig. 9: Note the tightening torques
Nm (lb.in)!
02474AXX
Fig. 10: Minimum clearance and installation position of the units
E
Q
E
E
Q
Q
E
Q Q
100 mm
(4 in)
100 mm
(4 in)
E
E
E
Q Q