MOVIDRIVE
®
MD_60A Operating Instructions
49
Startup with the DBG11A keypad
Startup
procedure
1. "0" signal at terminal X13:1 (DIØØ "/CONTROL.INHIBIT"), e.g.
by disconnecting the electronics terminal block X13.
CONTROL.INHIBIT
CURRENT:
0
A
2. Activate the startup menu by pressing the
←
and
→
keys on
the DBG11A at the same time.
STARTUP
→
IPOS_VARIABLES
←
3. Press the
→
key to commence the startup. The first window of
the startup menu appears. The menu commands are identified
by an * in the 4th position. Menu commands which only appear
in the startup menu start with "C", the other menu commands
have the number in the parameter list (page 280). Press the
↑
key to jump to the next menu command when you have worked
through a menu command.
STARTUP IS
BEING PREPARED
4. Select a parameter set, e.g. parameter set 1.
C00*
PARAM. SET 1
STARTUP
5. Set the operating mode, e.g. VFC1.
C01*
VFC1
OPER. MODE 1
6. Select the connected motor. If a 2 or 4-pole SEW motor is
connected, select the correct motor from the list. In the case of
a non-SEW motor or an SEW motor with more than four poles,
choose "NON-SEW MOTOR" in the selection list.
C02*
DV112M4
MOT. TYPE 1
C02*
NON-SEW
MOTOR
MOT. TYPE 1
7. Refer to the nameplate of the motor and enter the rated motor
voltage for the selected connection type.
Example: Nameplate 230
∆
/400
W
50 Hz
W
connection
→
Enter 400 V.
∆
connection, transition point at 50 Hz
→
Enter 230 V.
∆
connection, transition point at 87 Hz
→
Also enter 230 V. After
startup, first set parameter P302 "MAXIMUM SPEED 1" to the
value for 87 Hz and then start the drive.
Example: Nameplate 400
∆
/690
W
50 Hz
Only
∆
connection possible
→
Enter 400 V.
W
connection is not possible.
C03*
400
V
RATED MOT. VOLT. 1
8. Enter the rated frequency specified on the motor nameplate.
Example: 230
∆
/400
W
50 Hz
Enter 50 Hz in a
W
and
∆
connection.
C04*
50
Hz
RATED MOT. FREQ. 1
WITH SEW MOTORS
9. The motor values are stored for SEW 2 and 4-pole motors and
do not have to be entered.
WITH NON-SEW MOTORS
9. Enter the following data from the motor nameplate:
•
Rated motor current, note the connection type (
W
or
∆
).
•
Rated power of the motor
•
Power factor cos
ϕ
•
Rated speed of the motor
10. Enter the rated voltage of the supply system
C05*
400
V
RATED SYS. VOLT. 1
0
0
I