78
MOVIDRIVE
®
MD_60A Operating Instructions
General technical data
7
Technical Data
7.1
General technical data
The following table lists the technical data applicable to all MOVIDRIVE
®
MD_60A drive
inverters, regardless of type, version, size and performance.
MOVIDRIVE
®
MD_60A range of
units
MOVIDRIVE
®
MD_60A
All sizes
Interference immunity
To EN 61800-3
Interference emission with EMC-
compliant installation
According to class B limit to EN 55011 and EN 55014
To EN 61800-3
Sizes 1 and 2 on line side according to class A limit to EN
55011 and EN 55014 without further measures
Ambient temperature
ϑ
amb
Derating ambient temperature
Climate class
0 °C...+50 °C at I
D
= 100 % I
N
and f
PWM
= 4 kHz (VFC mode)
0 °C...+40 °C at I
D
= 125 % I
N
and f
PWM
= 4 kHz (VFC mode)
0 °C –+50 °C at I
D
= 100 % I
N
and f
PWM
= 8 kHz (CFC mode)
P
N
reduction: 3.0 % I
N
per K to max. 60 °C
EN 60721-3-3, class 3K3
Storage temperature
1)
ϑ
S
1) Connect to supply voltage for min. 5 minutes every 2 years if stored for long periods, otherwise the unit's
service life may be reduced.
-25 °C...+70 °C (EN 60721-3-3, class 3K3)
DBG keypad: -20 °C...+60 °C
Type of cooling (DIN 51751)
Forced cooling
Enclosure
Sizes1 to 3
EN 60529
Sizes 4 and 5
(NEMA1)
IP20
IP00 (power connections); IP10 with Plexiglas cover mounted
(supplied as standard)
Operating mode
DB (EN 60149-1-1 and 1-3)
Installation altitude
h
≤
1000 m (3300 ft)
I
N
reduction: 1 % per 100 m (330 ft)
from 1000 m (3300 ft) to max. 2000 m (6600 ft)
00891AXX
Fig. 53: MOVIDRIVE
®
MD_60A range of units
P
i
f
kVA
Hz
n