Three-point stepping controller
Switching controller for control of a valve (e.g. temperature control by means of motorized valve and gas-air mixture)
1.
Open
valve;
r
outputs
Y1 = 1
, Y2 = 0
2. Don’t move valve;
r
outputs Y1 = 0, Y2 = 0
3.
Close
valve;
r
outputs Y1 = 0,
Y2 = 1
To validate the adjusted X
p1
for the actuator response time, response time
T
m
must be adjusted. The smallest position-
ing step is 100ms.
Adjusting the neutral zone
Neutral zone X
sh
can be increased in case of excessive output switching. However, note that an increase the neutral
zone will reduce the control sensitivity.
For this reason, we recommend optimizing switching frequency (actuator wear) and control sensitivity.
Output Y1 (open)
Output Y2 (closed)
Three-point stepping controllers can be operated with or without position feedback Yp .
Schritt
3-point stepping controller
SchrittYP
3-point stepping controller with position feedback
whereby
Yp
is not used for control. The static characteristic of a three-point stepping controller is shown in Fig. : 3 .
The hysteresis shown in this diagram is practically unimportant, but can be calculated from the adjustable min. pulse
length T
puls
?
100ms.
X
Tpuls
Xp
Tm
sh
=
× ×
2
0 1
,
g
With
Tpuls
switched off, the shortest positioning step
Tpuls
is dependent of
Tm
,
Xsh
and
Xp
.
By varying
Xsh
, a required min. pulse length
Tpuls
can be realized:
X
Xp
Tpuls
Tm
sh
=
× ×
-
12 5
0 75
,
'
,
9499 040 50611
Controller
175
Controller behaviour
100%
0%
100%
0%
Y1
Â
Y2
Â
Xn100
Xn0
W0
Weff
W100
Xeff
Xp1
Xsh
Fig.: 3
Static
operating principle of a three-point
stepping controller
Set-point
Set-point
process value
process value
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...