6.6
Versions with integrated supply voltage
The potential-free supply voltage can energize a 2-wire transmitter or max. 4 control inputs. The output connections
can be selected with 3 S.I.L. switches:
Connections
Ü
*
Ö
Remarks
14(+)
12 (-)
T
open
closed
Only available, if INP1 is configured for current or thermocouple
4 (+)
1 (-)
D
closed
open
The voltage input of INP5 is not available
Factory setting:
Ü
= T,
*
= open,
Ö
= closed (T).
The unit must be withdrawn from the housing for changing
the switch positions.
The S.I.L. switches are located on the circuit board shown right.
* If A14/A12 is used for di1/di2, A12 must be connected with A1
6.7
Digital inputs and outputs (
r
connecting diagram)
The digital inputs and outputs must be energized from one or several 24 V DC sources. The current consumption is
5 mA per input. The max. load is 0,1 A per output. Examples:
Digital inputs (connector A)
Digital inputs and outputs at one voltage
source (e.g. connector B)
Digital inputs and outputs at two voltage
sources (e.g. connector B)
Electrical connections
9499 040 50611
Versions with integrated supply voltage
20
Energization of digital inputs (e.g. di1...di4)
2-wire transmitter connection (e.g. INP1)
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...