Inputs/outputs
Digital inputs (DPROG):
hide
Display suppression (with
hide
= 1 the page is not displayed during operation).
lock
Adjustment blocking (with
lock
= 1 the values are not adjustable by means of keys
ID
).
run
Program stop/run ( 0 = stop, 1 = run )
reset has highest priority
reset
Program continue/reset (0 = continue, 1 = reset )
preset
Program preset ( 1 = preset )
Digital outputs (DPROG):
run
Status program stop/run (0 = program stop ; 1 = program run)
reset
Status program reset (1 = program reset)
end
Status program end (1 = program end reached)
fkey
Status A/M key / interface function `fkey’ (:pressing key
H
causes switch-over (0 or 1))
do1... do6
status of control outputs in the actual segment
Analog inputs (DPROG):
PSet
Preset value for program
DBlock
Block number of 1st data function `DPROGD’
ProgNo
Required program number (recipe)
Analog inputs (DPROGD):
DBlock
Block number of cascadable data function `DPROGD’
Analog outputs (DPROG):
TNetto
Program time net (
]
T
run
)
TBrutt
Program time gross (
]
Trun +
]
Tstop)
TRest
Programmer rest time
SegNo
Actual segment number
ProgNo
Actual program number (recipe)
Analog outputs (DPROGD):
DBlock
Own block number
Parameter and configuration data
Parameter
DPROG
Description
Range
Default
PMode
Preset Mode:
Preset to segment
Pres.time
t
Preset to time
Pres.seg.
D0
Status of control outputs 6...1 with reset
0 / 1 per output
000000
Parameter
DPROGD
Description
Range
Default
ET
Unit
ET
Unit
Tp 1
Time for segment 1 (
Ü
)
0 ... 59 999
0:00
...
999:59
OFF
--:--
D 1
Status of control output values in segment 1 (
*
)
0 / 1 per output
000000
000000
Tp 2
Time for segment 2 (
Ü
)
0 ... 59 999
0:00
...
999:59
OFF
--:--
D 2
Status of control output values in segment 2 (
*
)
0 / 1 per output
000000
000000
...
Tp 10
Time for segment 10 (
Ü
)
0 ... 59 999
0:00
...
999:59
OFF
--:--
D 10
Status of control output values segment 10 (
*
)
0 / 1 per output
000000
000000
The time for a segment is entered in the engineering tool in seconds or minutes dependent of configuration (
Turbo
),
whereas entry into the unit is in Hrs:Min or Min:Sec. In addition to the range, a switch-off value can be entered (ET:
OFF/-32000; unit:
--:--
). When reaching a segment with a switch-off value, ‘
End
‘ is output.
9499 040 50611
Programmer
153
DPROG ( digital programmer ) / DPROGD ( DPROG data )
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...