19.7
RM_(RM200 - analog output module)
Function
RM_AO
handles the data from connected analog output modules.
Input and outputs
Analog inputs
Slotx
Connection of one of the
Slot
outputs of the RM 200 node (C_RM2x)
AO 1...AO 4
1st to 4th analog output signal
Digital outputs
et-err
0 = no engineering error detected
1 = engineering error (several RM module functions on a slot)
slotId
0 = correct slot assignment
1 = faulty slot assignment (wrong RM module fitted)
valid
0 = no data
1 = data could be received
fail 1
...
fail 4
Measurement error on channel 1 to 4 (e.g. sensor break)
Parameter and configuration data
Configuration
Description
Range
Default
MTyp
Module type
0: RM231-0 = 4 x 0/4...20 mA / 4 x 0...10 V
1: RM231-1 = 4 x 0/4...20 mA / 2 x 0...10 V / 2 x -10...10 V
2: RM231-2 = 4 x 0/4...20 mA / 4 x -10...10 V
OTyp 1
...
OTyp 4
Output signal
10: standard signal = 0 ... 10V
11: standard signal = -10 ... 10V
20: standard signal = 0 ... 20 mA
21: standard signal = 4 ... 20 mA
x0 1
Scaling start value input 1...input 4
-29 999 ... 999 999
0
...
x0 4
x100 1
Scaling end value input 1 ... input 4
-29 999 ... 999 999
100
...
x100 4
RM_(RM200 - analog output module)
KS98+ I/O extensions with CANopen
125
RM_(RM200 - analog output module)
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...