Configuration DPROG Description
Values
PwrUp
Behaviour after mains recovery
Continue program (default)
Cont prog
Search run in the actual segment
Cont seg
Continue at actual time
Cont time
PEnd
Behaviour at program end
stop after program end (default)
Stop
Reset after program end
Reset
Turbo
Time unit
Time = hours : minutes (default)
Hrs:Min
Time = minutes : seconds
Min:Sec
Cascading
Cascading APROGD function blocks permits realization of a programmer with any number of segments. The segment
sequence is dependent of the APROGD function block wiring (
r
see below ).
Recipes
Analog output ‘
ProgNo
‘, at which the actual recipe number is output, and one or several SELV2 function blocks can
be used to select a recipe the block number of which is switched to the APROG input (
r
see below). Selection of the
required recipe is possible via analog input ‘
ProgNo
‘ or recipe number, which can be entered via operation/inter-
face.
a
Recipe switch-over (new
ProgNo
) is effective only after programmer reset.
Entry of the recipe number via operation/interface is possible only, if analog input
ProgNo
is not connected.
g
If each recipe shall have a separate reset set-point (Wp0), function blocks REZEPT and VPARA can be
used as shown up. Note the calculation order (APROG
r
REZEPT
r
VPARA).
9499 040 50611
Programmer
147
APROG ( analog programmer ) / APROGD ( APROG data )
Recipe 1
Recipe 2
Recipe 3
Example of an analog programmer with 3 recipes à 20 segments
Segment 11 ... 20
Segment 1 ... 10
Segment n ... n+10
Example of an analog programmer with n segments
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...